DESCRIPTION

The CI-200 is a 24VDC Passive Infrared (PIR) occupancy sensor which controls 

lighting or HVAC systems based on occupancy and/or ambient light levels in a 

given area. 
PIR sensing systems are passive systems which react to changes in infrared 

energy (moving body heat) within the coverage area. PIR sensors must directly 

“see” motion of an occupant to detect them, so careful consideration must be 

given to sensor placement.

Coverage Patterns

The CI-200 has a multi-cell, multi-tier Fresnel lens with a field of view of 360°. 

The sensor has two lens pattern options. The Extended Range Lens will cover 

up to 1200 sq ft when mounted from 8-12ft. The High Density/Reduced Range 

Lens will cover up to 500 sq ft when mounted at 8-12ft. 
Coverage shown in the diagrams below is maximum and represents coverage 

for half-step walking motion, with no barriers or obstacles.

44 ft

Drawing Not to scale

24 ft

Extended Range Lens 

(Standard) CI-200

High Density/Reduced Range 

Lens CI-200-1

Call 800.879.8585 For Technical Support

Top View @ 8ft

Top View @ 8ft

Side View

Side View

Summary of Contents for CI-200

Page 1: ...emperature 32 to 131 F 0 to 55 C Time Delay Adjustment 15 seconds 30 minutes PIR Coverage Model CI 200 up to 1200ft2 Model CI 200 1 up to 500ft2 Light Level Adjustment 1 190FC Sensitivity Adjustment M...

Page 2: ...overage Patterns The CI 200 has a multi cell multi tier Fresnel lens with a field of view of 360 The sensor has two lens pattern options The Extended Range Lens will cover up to 1200 sq ft when mounte...

Page 3: ...more than 12 14ft you may start to significantly reduce sensitivity Often the best location to install a CI 200 in a closed office is off center see fig 1 Avoid placing a sensor directly in line with...

Page 4: ...ation of coverage in unwanted areas The mask is cut as needed and mounted onto anchor pins in the sensor s cover IMPORTANT Do not use the mask if full coverage is desired IMPORTANT Before securing the...

Page 5: ...a second load for occupancy and light level ambient light control connect BLUE wire from power pack to yellow wire on sensor BLUE wire from slave pack to blue wire on sensor BLACK wire from slave pack...

Page 6: ...nal adjustment leave the setting at maximum The controlled lights will then not be affected by ambient light levels To make the light level adjustment The final light level setting for normal operatio...

Page 7: ...problem may be in the sensor Turn Sensitivity and Time Delay to minimum and allow the sensor to time out If the lights turn off the sensor is working correctly See Unwanted Sensor Activations next pag...

Page 8: ...cy Sensor with High Density Reduced Range Lens BZ 50 Power Pack 120 277VAC 50 60Hz 20A ballast or incandescent B347D P Power Pack 347VAC 60Hz 150mA 15A ballast S120 277 347E P Slave Pack 120 277VAC 60...