The format column may be used to override the default numeric data format for the given record.
Standard printf style format strings may be used i.e. %f, %i, %X, etc. Leave this field empty to use
the default data format.
•
The format of the log file name is “YYYY
-MM-DD.csv.
”
•
A new file is created every day. Mount the MICRO SD drive to access / manage log files.
•
Files with a creation date older than
will be deleted. Folders, read-only files, and
hidden files are excluded.
•
File maintenance is triggered when a new file is created (file size is zero).
•
•
Unsupported data types will be blank. This may be observed in a log file if the RMA PLUS is not able
to read the representation (data type) of a member. This will be the case if the target device is not
present or the bus has yet to acquire the member attributes.
•
If the file nor:\Text.csv exists, enumerations will be logged as strings. If not, they will be logged as
their integer equivalent.
•
data points will display 99999 if an error exists.
Header
Format
Bus
Segment
Zone
Class
Instance
Member
Refresh Count
DEV 1 Hardware ID
1
0
0
1
1
1
0
TST 1 Tick
1
0
0
16
1
6
0
RTC 1 Timestamp
1
0
0
36
1
19
0
Figure 46 - DataLog.csv default configuration
The following is a sample from the file
“sd:
\DataLog\2018-01-25.csv
”
generated from the configuration
file above:
Time
DEV 1 Hardware ID
TST 1 Tick
RTC 1 Timestamp
0:00:00
118
224660111
570175200
0:00:05
118
224665131
570175205
0:00:10
118
224670111
570175210
0:00:15
118
224675081
570175215
0:00:20
118
224680101
570175220
0:00:25
118
224685121
570175225
0:00:30
118
224690096
570175230
0:00:35
118
224695116
570175235
0:00:40
118
224700081
570175240
0:00:45
118
224705106
570175245
Modbus® RTU
This feature is only available if the model number is RMAP-
2
AXX-XXXX.
If available, the RMA PLUS enables two Modbus® RTU channels on an adjacent RS-232 / RS-485
companion module. These channels may be independently configured as masters or slaves. Modbus®
RTU does not proxy requests. It interacts asynchronously with a user-defined data model loaded on
initialization and configured by way of a USBD gateway file.
As a Modbus® RTU slave, the RMA PLUS only implements the following Modbus® function codes:
•
3: Read Holding Registers
•
4: Read Input Registers
Summary of Contents for RMA PLUS RMAP-2A Series
Page 1: ...Version 1 0 PN 2042 8198 Page 1 of 75 DN 10 32813 RMA PLUS User Manual...
Page 8: ...Version 1 0 PN 2042 8198 Page 8 of 75 DN 10 32813...
Page 11: ...Version 1 0 PN 2042 8198 Page 11 of 75 DN 10 32813 Figure 3 Ground Wire Location...
Page 26: ...Version 1 0 PN 2042 8198 Page 26 of 75 DN 10 32813 Figure 22 RMA PLUS via USBD MICRO SD root...
Page 27: ...Version 1 0 PN 2042 8198 Page 27 of 75 DN 10 32813 Figure 23 RMA PLUS via USBD NOR FLASH root...
Page 42: ...Version 1 0 PN 2042 8198 Page 42 of 75 DN 10 32813 Figure 37 Default web page Index html...
Page 75: ...Version 1 0 PN 2042 8198 Page 75 of 75 DN 10 32813...