PM3 LEGACY™ 

PID CONTROLLER 

QUICK START 

GUIDE

For Confi gurations:

PM3_ _ [A,C,E,F,K] [A,C,J,K] -_ AAAN _ _ 

For assistance contact Watlow: www.watlow.com 

1-800-WATLOW2 (1-800-928-5692)

[email protected] 

Document #10-43056, Part #2152-6956

December, 2020

              1 - MOUNT TO PANEL

NOTE:  Mounting requires access to 
the back of the panel.

2 - CONNECT THE SENSOR INPUT

Connect your sensor as 
indicated in the diagram for 
your sensor input. Figure 
4 is an example illustrating 
the connection shown for a 
Thermocouple.

Thermocouple

S1

Figure 4: Thermocouple Wiring Example

Platinum 100Ω or 1000Ω RTD

20Ω max. round trip lead resistance

Process Voltage or Current 

Voltage: 0 to 50 mV or 0 to 10V@ 20kΩ
Current: 0 to 20 mA @ 100Ω

             3 - WIRE OUTPUT 1

Refer to the wiring diagram for your confi guration 
code and connect to the slots indicated.

PM3_ _  [E] _ _AAAN_ _: 
Mechanical Relay

5A Form C Relay 

PM3_ _ [C] _ _AAAN_ _: Switched DC or Open Collector

Figure 5: Switched DC Output Wiring

PM3_ _ _ [C ] _ AAAN_ _: 

Switched DC

4 - WIRE OUTPUT 2

PM3_ _ _ [J] _ AAAN_ _: 
Mechanical Relay 5A Form A Relay 

PM3_ _ [F] _ _ AAAN_ _: Universal Process

6 - CE DECLARATION OF CONFORMITY

5 - CONNECT POWER


+

S1

R1

T1

+

S1

volts

R1

T1

+

S1

amperes

R1

S3

2-wire

S1

T1

S1
R1

T1

S1

S3

S1

S2

3-wire

R1

X1

Y1

Internal Circuit

Common

Switched DC

Open Collector

W1

Power Supply

Load

Load

+

+

+

+

24V(dc)

F1
G1

H1

+

Internal Circuit

Voltage Load

Current Load

or

Load

Load

4 to 20mA

0 to 10 V

L1
K1

J1

Internal Circuit

Common

Normally

Open

Normally

Closed

AC

Load

Load

Internal Circuit Common

Normally Open

L2
K2

AC

Load

Confi guration Code: 

PM3 _ [1,2,3,4] _ _ _AAAN _ _

  1 or 2: 120-240 V (ac)
  3 or 4: 24 V (ac or dc)

CAUTION

Do not connect high voltage to a controller 

that requires low voltage.

 

Declaration of Conformity - Series EZ-ZONE

®

 PM   

WATLOW Electric Manufacturing Company 

       

1241 Bundy Blvd. Winona, MN 55987 USA 

 
Declares that the following product meets the essential requirements of the following European Union Directives by using  
the relevant standards show below to indicate compliance. 

Designation: 

Series EZ-ZONE

®

 PM (Panel Mount) 

r

o

 

r

e

tt

e

L

 

y

n

A

(

)

4

 

r

o

 

9

 ,

8

 ,

6

 ,

3

(

 

M

P

 :

s

r

e

b

m

u

N

 l

e

d

o

M

 number)(1, 2, 3 or 4)(A, C, E, F or K) (A, C, 

H, J or K) – (Any letter or number)(Any letter or number)(A, C, E, F or K)(A, C, 
H, J or K) (Any three letters or numbers) 

e

t

a

C

 

n

o

it

a

ll

a

t

s

n

,l

o

r

t

n

o

c

 

e

r

u

t

a

r

e

p

m

e

T

 :

n

o

it

a

c

if

i

s

s

a

l

C

gory II, Pollution degree 2, IP65 

Rated Voltage and Frequency: 

100 to 240 V~ (ac 50/60 Hz) 

or

 15 to 36 V

dc/ 24 V~ac 50/60 Hz 

Rated Power Consumption: 

10 VA maximum PM3, PM6 Models. 
14 VA maximum PM8, PM9, PM4 Models 

2014/30/EU Electromagnetic Compatibility Directive 

EN 61326-1:2013 

Electrical equipment for measurement, control and laboratory use – EMC 
requirements (Industrial Immunity, Class B Emissions).

 

IEC 61000-4-2:2008 

Electrostatic discharge immunity 

IEC 61000-4-3:2007 +A1/2008, 
A2/2010 

Radiated, radio-frequency electromagnetic field immunity 10V/M 80–1000 MHz, 3 V/M 
1.4–2.7 GHz 

IEC 61000-4-4:2012 

Electrical fast-transient / burst immunity 

IEC 61000-4-5:2014 +A1/2017 

Surge immunity 

IEC 61000-4-6:2013 + 
Corrigendum 2015 

Immunity to conducted disturbances induced by radio-frequency fields 

IEC 61000-4-11:2004 + A1/2017 Voltage dips, short interruptions and voltage variations immunity 
EN 61000-3-2:2014 

Limits for harmonic current emissions for equipment 

”

 16 Amps per phase 

EN 61000-3-3

1

:2013 + A1/2017 

Voltage fluctuations and flicker 

”

 16 Amps per phase 

SEMI F47-0812 

Specification for semiconductor sag immunity Figure R1-1 

1

For mechanical relay loads, cycle time may need to be extended up to 160 seconds to meet flicker requirements 

depending on load switched and source impedance. 

2014/35/EU Low-Voltage Directive 

EN 61010-1:2010

Safety Requirements of electrical equipment for measurement, control and 
laboratory use. Part 1: General requirements 

Compliance with 3rd Edition requirements with use of external surge suppressor installed on 230 Vac~ power line units.  

  Recommend minimum 1000 V peak to maximum 2000 V peak, 70 joules or better part be used.

 

Compliant with 2011/65/EU RoHS2 Directive Per 2012/19/EU W.E.E.E Directive 

 

 Please Recycle Properly. Models PM(4, 8 or 9)E contain a type BR1225 coin cell battery which shall be 

recycled at end of life per 2006/66/EC Battery Directive as amended by 2013/56/EU Directive. 
Models PM6XXXX – (B, E, F, G, H, J, K)XXXXXX where (X = any letter or number allowed above)

 

Include 

Bluetooth

®

 wireless technology and have been reviewed to the following additional requirements. 

2014/53/EU Radio Equipment Dire

ĐƟǀĞ

 (RED)

 

EN 61010-1:2010

 

Safety Requirements of electrical equipment for measurement, control and laboratory use.  
Part 1: General requirements 
Covering the essential requirements of article 3.1(a) or Directive 2014/53/EU 

EN 61326-1:2013   

Electrical equipment for measurement, control and laboratory use – EMC requirements 
(Industrial Immunity, Class A Emissions). 

CAUTION: This equipment not intended for use in residential environments and may not provide 
adequate protection to radio reception in such environments.

 

EN 301 489-1 V2.1.1     

ElectroMagnetic Compatibility (EMC) standard for radio equipment and services; Part 1: Common

technical requirements; Harmonized Standard covering the essential requirements of article 
3.1(b) of Directive 2014/53/EU and the essential requirements of article 6 of Directive 2014/30/EU

EN 301 489-17 V3.1.1    ElectroMagnetic Compatibility (EMC)

   standard for radio equipment and services; Part 17: 

Specific conditions for Broadband Data Transmission Systems; Harmonized Standard covering 
the essential requirements of article 3.1(b) of Directive 2014/53/EU 

EN 300 328 V1.9.1     

Electromagnetic compatibility and  Radio spectrum Matters (ERM); Wideband transmission 

systems; Data transmission equipment operating in the 2,4 GHz ISM band and using wide band 
modulation techniques; Harmonized EN covering the essential requirements of article 3.2 of the 
R&TTE Directive 
NVLAP Test Report 10928545H-A 

EN 300 328 V2.1.1  

 

Additional Receiver blocking test for to cover requirements for 2014/53/EU.   

NVLAP Test Report 11649468H-E 

 

Contains Module FCC ID: VPYLBZY Part 15C 2. 

Contains Module IC: 

772C-LBZY RSS 210 

 
Output Power:  Frequency Range 2402.0 

2480.0  

 

Output Power 0.001 Watts   Antenna gain: -0.6 dBi PCB antenna  

 

 

Doug

S

U

 ,

a

t

o

s

e

n

n

i

M

 ,

a

n

o

n

i

W

 

  

a

t

h

c

u

K

 

 

Name of Authorized Representative   

Place of Issue 

 

 

Director of Operations 

 

May 2018 

 

 

 
 
Signature of Authorized Representative 

Internal Circuit

Common

W2
Y2

Load

+

24V(dc)

PM3_ _ _ [C] _ AAAN_ _: Switched DC 

Internal Circuit Common

Normally Open

L2
K2

AC

Load

PM3_ _ _ [K] _ AAAN_ _: 
Solid State Relay 0.5A, Form A

Figure 3

Figure 1

are on the sides (see fi gure 2), then slide the base over 
the back of the controller. 

5.  Slide the mounting bracket over the controller with the 

screws aligned to the collar base.  Push the bracket gently 
but fi rmly until the hooks snap into the slots in the case.

6.  Tighten the two #6-19 x 1.5 in. screws with a phillips 

screwdriver until the device is fl ush to the panel 
(3 to 4 in-lbs torque).

7.  Reinstall the terminal connectors to their original locations. 

(Or fi rst connect fi eld wiring as indicated in this guide and 
then reinstall the connectors).

1.  Make the panel cutout using 

the measurements in fi gure 1.

2.  Remove the green terminal 

connectors and the mounting 
collar assembly. 

3.  Insert the controller into the 

panel cutout from the front.

4.  Orient the collar base so the fl at side 

faces front and the screw openings 

Figure 2

Collar Base

Terminal
Connectors

Mounting 
Bracket

Internal Circuit Common

Normally Open

L1
K1

AC

Load

PM3_ _ [K] _ _ AAAN_ _: 
Solid State Relay 0.5A, Form A

45.2 mm

(1.78 in.)

22.4 mm

(0.88 in.)

Summary of Contents for PM3 LEGACY

Page 1: ...Needed New PM3 text Needed PM3 LEGACY PID CONTROLLER QUICK START GUIDE For Configurations PM3_ _ A C E F K A C J K _ AAAN _ _ For assistance contact Watlow www watlow com 1 800 WATLOW2 1 800 928 5692 wintechsupport watlow com ...

Page 2: ...a phillips screwdriver until the device is flush to the panel 3 to 4 in lbs torque 7 Reinstall the terminal connectors to their original locations Or first connect field wiring as indicated in this guide and then reinstall the connectors 1 Make the panel cutout using the measurements in figure 1 2 Remove the green terminal connectors and the mounting collar assembly 3 Insert the controller into the pa...

Page 3: ...ing the connection shown for a Thermocouple Thermocouple S1 Figure 4 Thermocouple Wiring Example Platinum 100Ω or 1000Ω RTD 20Ω max round trip lead resistance Process Voltage or Current Voltage 0 to 50 mV or 0 to 10V 20kΩ Current 0 to 20 mA 100Ω S1 R1 T1 S1 volts R1 T1 S1 amperes R1 S3 2 wire S1 T1 S1 R1 T1 S1 S3 S1 S2 3 wire R1 ...

Page 4: ... Collector PM3_ _ F _ _ AAAN_ _ Universal Process X1 Y1 Internal Circuit Common Switched DC Open Collector W1 Power Supply Load Load 24V dc F1 G1 H1 Internal Circuit Voltage Load Current Load or Load Load 4 to 20mA 0 to 10 V Internal Circuit Common Normally Open L1 K1 AC Load PM3_ _ K _ _ AAAN_ _ Solid State Relay 0 5A Form A ng diagram for your configuration ct to the slots indicated PM3_ _ E _ _...

Page 5: ...N_ _ Mechanical Relay 5A Form A Relay Internal Circuit Common Normally Open L2 K2 AC Load Internal Circuit Common W2 Y2 Load 24V dc PM3_ _ _ C _ AAAN_ _ Switched DC Internal Circuit Common Normally Open L2 K2 AC Load PM3_ _ _ K _ AAAN_ _ Solid State Relay 0 5A Form A ...

Page 6: ...5 CONNECT POWER Configuration Code PM3 _ 1 2 3 4 _ _ _AAAN _ _ 1 or 2 120 240 V ac 3 or 4 24 V ac or dc CAUTION Do not connect high voltage to a controller that requires low voltage ...

Page 7: ...nd minimum 1000 V peak to maximum 2000 V peak 70 joules or better part be used Compliant with 2011 65 EU RoHS2 Directive Per 2012 19 EU W E E E Directive Please Recycle Properly Models PM 4 8 or 9 E contain a type BR1225 coin cell battery which shall be recycled at end of life per 2006 66 EC Battery Directive as amended by 2013 56 EU Directive Models PM6XXXX B E F G H J K XXXXXX where X any letter...

Page 8: ...d setting in left display Infinity Key Clears or silence alarm when active else return home 7 KEYPAD OVERVIEW For assistance contact Watlow www watlow com 1 507 494 5656 wintechsupport watlow com https www watlow com resources and support Technical Library Scan for full manual 1 2 5 6 Left Display Home at beginning displays process value PV Entering into menus displays the value or setting of param...

Page 9: ...alarm 4 me 6 sec to enter setup page start from home select alarm menu 1 to 4 select which alarm off deviation process select alarm type enter degrees select minimum set point both high low select alarm side to to to to to These instructions are not inclusive This Quick Start Guide QSG is meant to be a quick reference to show you how to navigate to frequently used areas of the controller As an exa...

Page 10: ...ome return home to to to to 6 sec to enter setup page 6 sec to enter setup page if thermocouple select tC if rtd 100 ohm select rtd if 3 leaded rtd select 3 select thermocouple type J K is letter H T is letter t return home OR ...

Page 11: ...e enter degrees select minimum set point enter degrees select maximum set point to to to to to 10 SET CONTROL LOOP 6 sec to enter setup page start from home select control loop menu off PID on off select heat and cool algorithms off bumpless manual user select control loop action on sensor failure enter degrees select minimum set point enter degrees select maximum set point to to to to to return h...

Page 12: ...fun output if alarm to to to to 11 SET OUTPUTS 6 sec to enter setup page start from home select output menu 1 or 2 select output number if heat or cool 20 if mechanical relay select time base heat cool alarm select function of output if alarm select which alarm 1 to 4 to to to to to return home ...

Page 13: ...lec alarm off d proc alarm to to to 12 SET ALARM 6 sec to enter setup page start from home select alarm menu 1 to 4 select which alarm off deviation process select alarm type enter degrees select minimum set point both high low select alarm sides to to to to to ...

Page 14: ...grees select high set point alarm active 1 to 4 select which alarm to to to to return home 13 SET ALARM SET POINTS 3 sec to enter operations page start from home select alarm menu enter degrees select low set point for dev alarm type enter degrees select high set point alarm active 1 to 4 select which alarm to to to to return home alternates ack alarm ...

Page 15: ...urn home auto entry after 3 sec 15 AUTOTUNE THE CONTROL LOOP return home to to to to 6 sec to enter setup page if thermocouple select tC if rtd 100 ohm select rtd if 3 leaded rtd select 3 select thermocouple type J K is letter H T is letter t return home OR start from home no yes select auto tune returns to no when complete tuning in progress to return home alternates ...