Watlow F4T Install & Troubleshooting
•
41
•
Chapter 6 Appendix
Chapter 6: Appendix
F4T Base Specifications
Line Voltage/Power (Minimum/Maximum Ratings)
• High voltage option: 100 to 240V~ (ac) 50/60Hz
• Low voltage option: 24 to 28V (~ ac) (
Î
dc), 50/60Hz
• Power consumption: 23 W, 54VA maximum
Environment
•
NEMA 4X/IP65 - front panel mount configuration only
•
0 to 122°F (-18 to 50°C) operating temperature
•
-40 to 185°F (-40 to 85°C) storage temperature
• 0 to 90% RH, non-condensing
Agency Approvals
• UL
®
/EN 61010 Listed, File E185611 QUYX
• UL
®
508 Reviewed
•
CSA CC.C#14, File 158031
•
FM Class 3545 (configurations with limit modules)
•
AMS 2750 E compliant: Analog input process values. Tip: Maximize field calibration accu
-
racy and uniformity by using advanced F4T features such as Calibration Offset and Linear-
ization Function Blocks. Refer to user manual for details.
• RoHS by design, China RoHS Level 2, W.E.E.E.
• CE
• Windows
®
Hardware Certification
User Interface
• 4.3 inch TFT PCAP color graphic touch screen
• LED backlife >50K hours
• 4 keys: Home, Main Menu, Back, Help
Control Loops
• 1 to 4 PID or ON-OFF control loops
• 0 to 6 Limit loops
• User-selectable action: heat, cool or heat/cool
• Auto-tune with TRU-TUNE+ adaptive control
Control Loops and Over-temperature Limits
• Input sampling: 10Hz
• Output update: 10Hz
6
Anderson-Bolds ~ 216-360-9800