901
°F or °C, System
r/w
0
°F
1
°C
103
% Power Output 1A, Status
r
Value
107
% Power Output 1B, Status
r
Value
3050
Activate Message, Digital Input 1
r/w
0
Message 1
1
Message 2
2
Message 3
3
Message 4
3051
Activate Message, Digital Input 2
r/w
0
Message 1
1
Messag
e 2
2
Message 3
3
Message 4
3052
Activate Message, Digital Input 3
r/w
0
Message 1
1
Message 2
2
Message 3
3
Message 4
3053
Activate Message, Digital Input 4
r/w
0
Message 1
1
Message 2
2
Message 3
3
Message 4
303
Alarm 1 High Deviation, Alarm Set Points
r/w
1 to 30000
303
Alarm 1 High Set Point, Alarm Set Points
r/w
<per sensor> to Alarm 1 Low Set Point
303
Alarm 1 Maximum High Rate, Alarm Set Points
r/w
Alarm 1 Low Maximum Rate +1 to 30000
302
Alarm 1 Low Deviation, Alarm Set Points
r/w
-19999 to -1
302
Alarm 1 Low Set Point, Alarm Set Points
r/w
<per sensor> to Alarm 1 High Set Point
302
Alarm 1 Maximum Low Rate, Alarm Set Points
r/w
-19999 to Alarm 1 Maximum Rate High -1
102
Alarm 1, Status
r
0
Off
1
Alarm High
2
Alarm Low
322
Alarm 2 High Deviation, Alarm Set Points
r/w
1 to 30000
322
Alarm 2 High Set Point, Alarm Set Points
r/w
<per sensor> to Alarm 2 Low Set Point
322
Alarm 2 Maximum High Rate, Alarm Set Points
r/w
Alarm 2 Low Maximum Rate +1 to 30000
321
Alarm 2 Low Deviation, Alarm Set Points
r/w
-9999 to -1
321
Alarm 2 Low Set Point, Alarm Set Points
r/w
<per sensor> to Alarm 2 High Set Point
321
Alarm 2 Maximum Low Rate, Alarm Set Points
r/w
-19999 to Alarm 2 Maximum Rate High -1
106
Alarm 2, Status
r
0
Off
1
Alarm High
2
Alarm Low
703
Alarm Hysteresis, Alarm Output 1
r/w
1 to 9999
720
Alarm Hysteresis, Alarm Output 2
r/w
1 to 9999
707
Alarm Logic, Alarm Output 1
r/w
0
Open on Alarm
1
Close on Alarm
724
Alarm Logic, Alarm Output 2
r/w
0
Open on Alarm
1
Close on Alarm
708
Alarm Messages, Alarm Output 1
r/w
0
Yes on Main Page
1
No
725
Alarm Messages, Alarm Output 2
r/w
0
Yes on Main Page
1
No
706
Alarm Sides, Alarm Output 1
r/w
0
Both
1
Low
2
High
723
Alarm Sides, Alarm Output 2
r/w
0
Both
1
Low
2
High
716
Alarm Source, Alarm Output 1
r/w
0
Input 1
1
Input 2
2
Input 3
733
Alarm Source, Alarm Output 2
r/w
0
Input 1
1
Input 2
2
Input 3
702
Alarm Type, Alarm Output 1
r/w
0
Off
1
Process
2
Deviation
3
Maximum Rate
719
Alarm Type, Alarm Output 2
r/w
0
Off
1
Process
2
Deviation
3
Maximum Rate
836
Analog Range, Retransmit Output 1
r/w
0
4 to 20mA
1
0 to 20mA
2
0 to 5V
3
1 to 5V
4
0 to 10V
837
Analog Range, Retransmit Output 2
r/w
0
4 to 20mA
1
0 to 20mA
2
0 to 5V
3
1 to 5V
4
0 to 10V
200
Auto/Manual Mode, Status
r/w
1
Auto Mode
2
Manual
1915
Auto/Manual Slidewire Calibration, Analog Input 3 r/w
r/w
0
Skip Calibration
1
Automatic
2
Manual
305
Autotune PID
r/w
0
Tune Off
9 . 2
■
C o m m u n i c a t i o n s
Wa t l o w S e r i e s F 4 P
Series F4P Modbus Registers
Parameters Sorted Alphabetically
A list of all Modbus registers in numerical order follows this alphabetical list. Register numbers listed are
relative. Add 40001 to convert to absolute addesses. For more information about parameters, see the Index.
Summary of Contents for F4P Series
Page 4: ...ii Table of Contents Watlow Series F4P Notes...
Page 14: ...2 8 Operating from the Front Panel Watlow Series F4P Notes...
Page 58: ...6 32 Parameters Watlow Series F4P Notes...
Page 77: ...Watlow Series F4P Features 7 19 Notes...
Page 78: ...7 20 Features Watlow Series F4P Notes...
Page 94: ...8 16 Installation and Wiring Watlow Series F4P Notes...