5 . 6
■
F a c t o r y P a g e
Wa t l o w S e r i e s F 4 P
7. Press the Right Key
.
at the Calibrate Output 1B
prompt. At the 10.000V prompt press
.
once. Use
the Up Key
>
or the Down Key
<
to adjust the
display to the reading on the volt/ammeter. The
controller should stabilize within one second. Repeat
until the volt/ammeter reads 10.000V. Press
.
to
store the value.
8. Rewire for operation and verify calibration.
Retransmit Output Procedure
Equipment
• Precision volt/ammeter with 3.5-digit resolution.
Retransmit 1 Setup and Calibration
1. Connect the correct power supply to terminals 1, 2
and 3 (see the Wiring Chapter and the Appendix).
Milliamperes
2. Connect the volt/ammeter to terminals 50 (+) and 49
(-).
3. Press the Right Key
.
at the Calibrate
Rexmit 1 prompt. At the 4.000mA prompt press
.
once. Use the Up Key
>
or the Down Key
<
to
adjust the display to the reading on the
volt/ammeter. The controller should stabilize within
one second. Repeat until the volt/ammeter reads
4.000mA. Press
.
to store the value.
4. Press the Right Key
.
at the Calibrate Rexmit 1
prompt. At the 20.000mA prompt press
.
once. Use
the Up Key
>
or the Down Key
<
to adjust the
display to the reading on the volt/ammeter. The
controller should stabilize within one second. Repeat
until the volt/ammeter reads 20.000mA. Press
.
to
store the value.
Volts
5. Connect the volt/ammeter to terminals 48 (+) and 49
(-).
6. Press the Right Key
.
at the Calibrate Rexmit 1
prompt. At the 1.000V prompt press
.
once. Use the
Up Key
>
or the Down Key
<
to adjust the display
to the reading on the volt/ammeter. The controller
should stabilize within one second. Repeat until the
volt/ammeter reads 1.000V. Press
.
to store the
value.
7. Press the Right Key
.
at the Calibrate Rexmit 1
prompt. At the 10.000V prompt press
.
once. Use
the Up Key
>
or the Down Key
<
to adjust the
display to the reading on the volt/ammeter. The
controller should stabilize within one second. Repeat
until the volt/ammeter reads 10.000V. Press
.
to
store the value.
8. Rewire for operation and verify calibration.
Retransmit 2 Setup and Calibration
1. Connect the correct power supply to terminals 1, 2 and
3 (see the Installing and Wiring Chapter and the
Appendix).
Milliamperes
2. Connect the volt/ammeter to terminals 47 (+) and 46
(-).
3. Press the Right Key
.
at the Calibrate Rexmit 2
prompt. At the 4.000mA prompt press
.
once. Use
the Up Key
>
or the Down Key
<
to adjust the
display to the reading on the volt/ammeter. The
controller should stabilize within one second. Repeat
until the volt/ammeter reads 4.000mA. Press
.
to
store the value.
4. Press the Right Key
.
at the Calibrate Rexmit 2
prompt. At the 20.000mA prompt press
.
once. Use
the Up Key
>
or the Down Key
<
to adjust the
display to the reading on the volt/ammeter. The
controller should stabilize within one second. Repeat
until the volt/ammeter reads 20.000mA. Press
.
to
store the value.
Volts
5. Connect the volt/ammeter to terminals 45 (+) and 46
(-).
6. Press the Right Key
.
at the Calibrate Rexmit 2
prompt. At the 1.000V prompt press
.
once. Use the
Up Key
>
or the Down Key
<
to adjust the display
to the reading on the volt/ammeter. The controller
should stabilize within one second. Repeat until the
volt/ammeter reads 1.000V. Press
.
to store the
value.
7. Press the Right Key
.
at the Calibrate Rexmit 2
prompt. At the 10.000V prompt press
.
once. Use
the Up Key
>
or the Down Key
<
to adjust the
display to the reading on the volt/ammeter. The
controller should stabilize within one second. Repeat
until the volt/ammeter reads 10.000V. Press
.
to
store the value.
8. Rewire for operation and verify calibration.
Summary of Contents for F4P Series
Page 4: ...ii Table of Contents Watlow Series F4P Notes...
Page 14: ...2 8 Operating from the Front Panel Watlow Series F4P Notes...
Page 58: ...6 32 Parameters Watlow Series F4P Notes...
Page 77: ...Watlow Series F4P Features 7 19 Notes...
Page 78: ...7 20 Features Watlow Series F4P Notes...
Page 94: ...8 16 Installation and Wiring Watlow Series F4P Notes...