Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[SFn;A]
[SFn.A]
Action (1 to 8)
Source Function A
Set the event or func-
tion that will trigger the
action.
[[nonE]
None (61)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[lim]
Limit (126)
[`lgC]
Logic (239)
[tMr]
Timer (244)
[`uAr]
Variable (245)
None
1590
[offset 20]
0x6E
(110)
1 to 8
6
- - - -
10006
uint
RWES
[`Si;A]
[ Si.A]
Action (1 to 8)
Source Instance A
Set the instance of the
function selected above.
1 to 24
1
1582
[offset 20]
0x6E
(110)
1 to 8
2
- - - -
10002
uint
RWES
[`S2;A]
[ SZ.A]
Action (1 to 8)
Source Zone A
Set the zone of the func-
tion selected above.
0 to 16
0
1592
[offset 20]
0x6E
(110)
1 to 8
7
- - - -
10007
uint
RWES
[`LEu]
[ LEv]
Action (1 to 8)
Active Level
Set the action that will
be considered a true
state.
[LoW]
Low (53)
[high]
High (37)
High
1580
[offset 20]
0x6E
(110)
1 to 8
1
137
10001
uint
RWES
[Lim]
[`Set]
Limit Menu
[`L;Sd]
[ L.Sd]
Limit (1 to 4)
Sides
Select which side or
sides of the process val-
ue will be monitored.
[both]
Both (13)
[high]
High (37)
[LoW]
Low (53)
Both
728
[offset 30]
0x70 (112)
1 to 4
5
40
12005
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set