![Watlow EZ-ZONE RMC User Manual Download Page 62](http://html1.mh-extra.com/html/watlow/ez-zone-rmc/ez-zone-rmc_user-manual_3748884062.webp)
Watlow EZ-ZONE
®
RMC Module
•
59
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1 to 4)
Sensor Type
Set the analog sensor
type to match the device
wired to this input.
Note:
There is no open sensor
protection for process
inputs.
[`oFF]
Off (62)
[``tC]
Thermocouple (95)
[`mu]
Millivolts (56)
[uolT]
Volts dc (104)
[`MA]
Milliamps dc (112)
[r0;1H]
RTD 100 Ω (113)
[r1;0H]
RTD 1,000 Ω (114)
[`Pot]
Potentiometer 1 kΩ
(155)
[thEr]
Thermistor (229)
Thermo-
couple or
Thermis-
tor
368
[offset 90]
0x68 (104)
1 to 4
5
3
4005
uint
RWES
[`Lin]
[ Lin]
Analog Input (1 to 4)
TC Linearization
Set the linearization to
match the thermocouple
wired to this input.
[```b]
B (11)
[```H]
K (48)
[```C]
C (15)
[```n]
N (58)
[```d]
D (23)
[```r]
R (80)
[```E]
E (26)
[```S]
S (84)
[```F]
F (30)
[```t]
T (93)
[```J]
J (46)
J
370
[offset 90]
0x68 (104)
1 to 4
6
4
4006
uint
RWES
[`Rt;L]
[ rt.L]
Analog Input (1 to 4)
RTD Leads
Set to match the num-
ber of leads on the RTD
wired to this input.
[```2]
2 (1)
[```3]
3 (2)
2
372
[offset 90]
0x68 (104)
1 to 4
7
- - - -
4007
uint
RWES
[Unit]
[Unit]
Analog Input (1 to 4)
Units
Set the type of units the
sensor will measure.
[`A;tP]
Absolute Temperature
(1540)
[``rh]
Relative Humidity
(1538)
[`Pro]
Process (75)
[PWr]
Power (73)
Process
442
[offset 90]
0x68 (104)
1 to 4
0x2A (42)
5
4042
uint
RWES
[`S;Lo]
[ S.Lo]
Analog Input (1 to 4)
Scale Low
Set the low scale for pro-
cess inputs. This value,
in millivolts, volts or mil-
liamps, will correspond
to the Range Low output
of this function block.
-100.0 to 1,000.0
0.0
388
[offset 90]
0x68 (104)
1 to 4
0xF (15)
6
4015
float
RWES
[`S;hi]
[ S.hi]
Analog Input (1 to 4)
Scale High
Set the high scale for
process inputs. This
value, in millivolts, volts
or milliamperes, will
correspond to the Range
High output of this func-
tion block.
-100.0 to 1,000.0
20.0
390
[offset 90]
0x68 (104)
1 to 4
0x10 (16)
7
4016
float
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set