Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`PAr]
[ PAr]
Communications
Parity
Set the parity of this
controller to match the
parity of the serial net-
work.
Note:
Used by Modbus RTU
protocol.
[none]
None (61)
[EuEn]
Even (191)
[`odd]
Odd (192)
None
2826
0x96 (150)
1
4
- - - -
17003
uint
RWE
[`nU;S]
[ nV.S]
Communications
Non-volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM.
Note:
Used by Modbus RTU
protocol.
[`yes]
Yes (106)
[``no]
No (59)
Yes
2834
0x96 (150)
1 to 2
8
198
17051
uint
RWE
[M;hL]
[M.hL]
Communications
Modbus Word Order
Select the word order of
the two 16-bit words in
the floating-point values.
Note:
Used by Modbus RTU
protocol.
[hiLo]
Word High Low (1330)
[Lohi]
Word Low High (1331)
Low High 2828
0x96 (150)
1
5
- - - -
17043
uint
RWE
[`C_F]
[ C_F]
Communications
Display Units
Select which scale to use
for temperature passed
over communications
port 2.
Note:
Used by Modbus RTU
protocol.
[```F]
°F (30)
[```C]
°C (15)
°F
2830
0x96 (150)
1
6
199
17050
uint
RWE
No Dis-
play
Communications
Protocol
Select the communica-
tions protocol.
Standard Bus (1286)
Modbus RTU Word (1057)
1
2832
- - - -
- - - -
17009
uint
RWE
No Dis-
play
Communications
Modbus Address
Select the Modbus ad-
dress.
Note:
Used by Modbus RTU
protocol.
1 to 247
1
2822
- - - -
- - - -
17007
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set