D8 Series User’s Guide
Chapter 7: Troubleshooting and Reconfiguring
150
INPUT RANGE
RESISTOR VALUES
RC
RD
0 to 5VDC
39.2kΩ
475.0Ω
0 to 10VDC
49.9kΩ
301.0Ω
Resistor tolerance: ±0.1%
RP#
RD
Table 7.8
– Resistor Locations for Voltage Inputs
LOOP
RESISTOR LOCATIONS
RC
RD
1
R58
RP1
2
R56
RP2
3
R54
RP3
4
R52
RP4
5
R50
RP5
6
R48
RP6
7
R46
RP7
8
R44
RP8
RTD Inputs
Each RTD input has three scaling resistors installed: one each at RA, RB and RC for the input. RA
and RB are a matched pair of resistors installed in the resistor pack (RP) location as shown in the
illustration below.
Resistor values:
•
RA/RB:
25kΩ
•
RC:
18.2Ω
Resistor tolerances:
•
RA/RB:
Matched to 0.02% (±5 ppm/°C) with absolute tolerance of 0.1% (±25 ppm/°C)
•
RC:
Accurate to 0.05% (±5ppm/°C)
RP#
RA RB
Table 7.9
– Resistor Locations for RTD Inputs