D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
103
Power Up Alarm Delay
l
Power up alarm
r
delay
b
0 min
Specify how long to delay high, low and deviation alarms on all loops during powerup. This feature
does not delay failed sensor alarms.
Values:
0 to 60 minutes
Default:
0
DeviceNet™ Object:
Global (6B hex)
Power Up Loop Mode
l
Power up loop
r
mode
b
off
Choose the power-up state of the control outputs.
Values:
See Table 6.5.
Default:
off
(0)
DeviceNet™ Object:
Global (6B hex)
WARNING!
Do not set the controller to start from memory if it might be unsafe for the
control outputs to be on upon power up.
Table 6.5
– Power Up Loop Modes
DISPLAY
VALUE
DeviceNet™
VALUE
DESCRIPTION
off
0
Upon powerup, all loops are set to manual mode at 0 percent output.
from memory
1
Upon powerup, all loops are restored to the previous control mode
and output power level.