CLS200 Series User’s Guide
Chapter 4: Setup
92
Low Deviation Alarm Output Number
Choose a digital output to activate when the low deviation alarm occurs, if desired.
ALARM
01 LO DEV ALARM
OUTPUT ? NONE
Selectable values:
NONE
, or any output from
1
to
34
not enabled for closed-loop control or for the
Serial DAC clock.
Low Process Alarm Setpoint
Set a low process alarm setpoint. See
ALARM
01 LO PROC ALARM
SETPT? 0
Selectable values:
Any value within the input sensor’s range.
Low Process Alarm Type
Select an alarm type for the low process alarm.
ALARM
01 LO PROC ALARM
TYPE ? OFF
Selectable values:
ALARM
,
CONTROL
or
OFF
.
Low Process Alarm Output Number
Choose a digital output to activate when the low process alarm occurs, if desired.
ALARM
01 LO PROC ALARM
OUTPUT ? NONE
Selectable values:
NONE
, or any output from
1
to
34
not enabled for closed-loop control or for the
Serial DAC clock.
Alarm Deadband
Set an alarm deadband. This deadband value applies to the high process, low process, high
deviation and low deviation alarms for the loop. Use the alarm deadband to avoid repeated alarms
as the process variable cycles around an alarm value.