CLS200 Series User’s Guide
Chapter 4: Setup
71
Keyboard Lock Status
Set this parameter to ON to disable the
CHNG SP
,
MAN/AUTO
, and
RAMP/SOAK
keys on the
keypad. If the keys are disabled, pressing them has no effect. If you want to use these functions,
turn off the keyboard lock.
ALARM
KEYBOARD LOCK
STATUS ? OFF
Selectable values:
ON
or
OFF
.
Power Up Output Status
WARNING!
Do not set the controller to start from memory if it may be unsafe for your
process to have outputs on upon power-up.
Set the initial power-up state of the control outputs. If you choose
OFF
, all loops are initially set to
manual mode at 0% output. If you choose
MEMORY
, the loops are restored to the control status and
output value prior to powering down.
In Case of a Power Failure on page 130
for information about how this feature affects ramp/
soak profiles.
ALARM
POWER UP OUTPUT
STATUS ? OFF
Selectable values:
OFF
or
MEMORY
.
Process Power Digital Input
To enable the thermocouple short detection feature, select a digital input (1 to 8). Connect the
specified input to a device that pulls the input low when the process power is on. A short is indicated
when the process power is on and the temperature does not rise as expected.
If the controller determines that there is a thermocouple short, it sets the loop to manual mode at the
power level set for the
SENSOR FAIL HT OUTPUT
or
SENSOR FAIL CL OUTPUT
parameter in
the
SETUP LOOP OUTPUTS
menu.
ALARM
PROCESS POWER
DIGIN ? NONE
Selectable values:
1
to
8
, or
NONE
.