Name
Description
Read (?) and/or Write (=) Syntax
Range
data.1
data.2
Modbus
Address
Ramping Controller Prompt Table
981,
982,
983, 984
Data Communications with the Watlow Series 988 Family
Command Summary Series 981-984, Chapter 5
5.4
ANUN Alarm Annunciation ? <sp> ANUN <cr>
0 = off
725
= <sp> ANUN <sp> data.2 <cr>
1 = on
Default: on
AOUT Analog Output 3
? <sp> AOUT <cr>
0 = Retransmit Process Input 1
743
Retransmit Function = <sp> AOUT <sp> data.2 <cr>
1 = Retransmit Set Point 1
2 = off
3 = Retransmit Process Input 2
Default: 0
ARH
Retransmit
? <sp> ARH <cr>
ARL to 9999
745
Range High
= <sp> ARH <sp> data.2 <cr>
Default: RH1 or RH2 per AOUT
ARL
Retransmit
? <sp> ARL <cr>
-999 to ARH
744
Range Low
= <sp> ARL <sp> data.2 <cr>
Default: RL1 or RL2 per AOUT
ATSP
Auto-tune
? <sp> ATSP <cr>
50 to 150%
304
Set Point %
= <sp> ATSP <sp> data.2 <cr>
Default: 90%
AUT
Auto-tune
? <sp> AUT <cr>
0 = No auto-tuning
305
= <sp> AUT <sp> data.2 <cr>
1 = Tune PID
Default: off
C1
Input 1 Value
? <sp> C1 <cr>
Based on IN1 range ; RL1 to RH1
100
C2
Input 2 Value
? <sp> C2 <cr>
Based on IN2 range ; RL2 to RH2
104
CAL1
Input 1 Calibration
? <sp> CAL1 <cr>
-999
°
F to 999
°
F
605
Offset
= <sp> CAL1 <sp> data.2 <cr>
-555
°
C to 555
°
C
-999 units to 999 units
Default: 0
CAL2
Input 2 Calibration
? <sp> CAL2 <cr>
-999
°
F to 999
°
F
615
Offset
= <sp> CAL2 <sp> data.2 <cr>
-555
°
C to 555
°
C
-999 units to 999 units
Default: 0
CF
Degrees Select
? <sp> CF <cr>
0 = Display
°
F
901
Display Loop
= <sp> CF <sp> data.2 <cr>
1 = Display
°
C
Default: 0
CSP
Current Profile
? <sp> CSP <cr>
RL1 to RH1
1202
Set Point
CT1
Cycle Time
? <sp> CT1 <cr>
S.S. relay or open col:
506
Output 1
= <sp> CT1 <sp> data.2 <cr>
0.0 = Burst firing, or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.
CT2
Cycle Time
? <sp> CT2 <cr>
S.S. relay or open col:
516
Output 2
= <sp> CT2 <sp> data.2 <cr>
0.0 = Burst firing, or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.
DATE
Factory Test Date
? <sp> DATE <cr>
xxyy
5
xx = week
yy = year
DB
Dead Band PID
? <sp> DB <cr>
-999
°
F to 999
°
F
505
Heat/Cool
= <sp> DB <sp> data.2 <cr>
-555
°
C to 555
°
C
-999 units to 999 units
Default: 0
°
F, 0
°
C, or 0 units
DE1
Derivative
? <sp> DE1 <cr>
0.00 to 9.99 minutes
503
Output 1 PID
= <sp> DE1 <sp> data.2 <cr>
Default: 0.00
Table 5.4 -
ANUN to DE1
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.