Calibrating the System—Fixed Mode
1
2
Use the illustrations and instructions to verify that
the system is calibrated for fixed mode.
When operating the system:
•
Always start the system in auto or unload mode.
•
Always circulate enough cool water to regulate
the compressor oil temperature during operation.
•
Never operate the system with the compressor oil
temperature above 250°F (121°C).
1 Toggle the auto-sync switch to the
Unload
position to make sure that the air pressure
decreases to the unload mode value—typically
40 psi (2.8 bar).
2 Toggle the auto-sync switch to the
Fixed
position to make sure that the air pressure
increases to the fixed mode value—typically
145 to 150 psi (10 bar).
3 Verify that the system operates as expected in
both modes when you vary the engine speed.