background image

IM1022AN   01/13

Installation Information

Water Piping Connections

Hot Water Connections

Electrical

Startup Procedures

Troubleshooting

Preventive Maintenance

COMPACT

Water Source/Geothermal Heat Pump

 • 

R-410A 

Refrigerant

 

•  Commercial 0.75-6 Ton

En

vision

2

 C

ompact Ins

tallation Manual

s

Summary of Contents for envision 2 compact

Page 1: ... Water Piping Connections Hot Water Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance COMPACT Water Source Geothermal Heat Pump R 410A Refrigerant Commercial 0 75 6 Ton Envision 2 Compact Installation Manual s ...

Page 2: ......

Page 3: ...nd Water Systems 14 Hot Water Generator Connections 15 Freeze Detection 17 Electrical Connections 17 Electrical Data 18 Blower Performance Data 21 Wiring Schematics 26 Controls 31 Unit Startup 40 Operating Limits 41 Operating Parameters 41 Pressure Drop 43 Reference Calculations and Legend 44 Refrigerant Circuit Guideline 44 Compressor and Thermistor Resistance 45 Heat of Extraction Rejection Data...

Page 4: ...lower 015 072 Water Coil Option C Copper D Insulated Copper N Cupronickel P Insulated Cupronickel NOTES Phase guard only available on 208 230 60 3 460 60 3 and 575 60 3 Vintage A PSC 5 Speed ECM Motor B Variable Speed ECM Motor Non Standard Option Details SS Standard Option Drain Pan Option 0 Composite No Secondary Connection 1 Composite Secondary Connection 2 Stainless Steel No Secondary Connecti...

Page 5: ...Examine units for shipping damage removing the units from the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Safety Considerations General Installation Information Vertical Unit Mounting 2 in PEX Foam Unit Location Locate the unit in an indoor area that ...

Page 6: ...8 7 8 7 8 6 Standard filter rails for open return applications Deluxe filter rack for ductable return applications 2 61 cm Service Access Left Return Right Return opposite side 2 61 cm Alternate Service Access Field installed duct flange ACCESS PANEL ACCESS PANEL ACCESS PANEL Front View Left Return Top View Right Return Top View Left Return P Q B R N A Front View Right Return U T C D E H F G 1 4 i...

Page 7: ... 6 1 5 3 9 8 2 0 18 1 14 0 2 0 cm 5 6 25 4 25 4 15 5 13 5 24 9 5 1 46 0 35 6 5 1 015 018 in 2 2 14 0 14 0 6 1 4 5 7 7 2 0 22 1 22 0 1 9 cm 5 6 35 6 35 6 15 5 11 4 19 6 5 1 56 1 55 9 4 8 024 030 in 2 2 14 0 14 0 6 1 4 5 7 7 2 0 22 1 26 1 1 8 cm 5 6 35 6 35 6 15 5 11 4 19 6 5 1 56 1 66 3 4 6 036 038 in 2 2 18 0 18 0 6 6 4 6 6 3 1 6 28 1 26 1 2 0 cm 5 6 45 7 45 7 16 8 11 7 16 0 4 1 71 4 66 3 5 1 042 ...

Page 8: ...Front CMP AP CMP AP AP AP AIR COIL SIDE AIR COIL SIDE 0 5 in 1 3 cm knockout 1 in 2 5 cm knockout 1 in 2 5 cm knockout 0 5 in 1 3 cm knockout BP BP FILTER RACK FILTER RACK Standard filter rails Standard filter rails Deluxe filter rack option shown Deluxe filter rack option shown Deluxe filter rack option shown B B C C L M N P L M P N A L M P N C L M C A P N D E J A 1 7 in 5 3 cm 1 7 in 5 3 cm H 2 ...

Page 9: ...15 2 41 7 36 8 5 1 3 6 1 9 015 018 in 6 7 10 5 9 4 4 9 27 4 16 6 2 0 1 4 3 4 cm 17 0 26 7 23 9 12 4 69 6 42 2 5 1 3 6 1 9 024 030 in 6 7 10 5 9 4 4 9 30 4 16 6 2 0 1 5 3 4 cm 17 0 26 7 23 9 12 4 77 2 42 2 5 1 3 8 1 9 036 038 in 4 9 13 6 13 2 4 6 35 4 18 6 2 3 1 4 3 4 cm 12 4 34 5 33 5 11 7 89 9 47 2 5 8 3 6 1 9 042 049 in 4 9 13 6 13 2 4 6 40 4 18 6 2 3 1 4 3 4 cm 12 4 34 5 33 5 11 7 102 6 47 2 5 ...

Page 10: ...taching the hanger rods to the bracket a double nut is required since vibration could loosen a single nut To allow filter access install hanger brackets as illustrated in the Hanger Bracket Locations section The unit should be pitched approximately 1 4 in towards the drain in both directions to facilitate the removal of condensate Use only the bolts provided in the kit to attach hanger brackets Th...

Page 11: ...4 8 71 4 62 0 74 4 Dual Capacity 026 in 99S500A04 45 8 25 1 21 4 n a cm 116 3 63 8 54 4 n a 038 in 99S500A03 48 8 28 1 24 4 n a cm 124 0 71 4 62 0 n a 049 in 99S500A04 53 8 28 1 24 4 n a cm 136 7 71 4 62 0 n a 064 in 99S500A04 61 8 28 1 24 4 n a cm 157 0 71 4 62 0 n a 072 in 99S500A03 68 8 28 1 24 4 34 0 cm 174 8 71 4 62 0 74 4 3 16 12 Weight Distribution Model Vertical Weight Horizontal Weight Ho...

Page 12: ... unit whenever the unit operates To assure proper flow use pressure temperature ports to determine the flow rate These ports should be located at the supply and return water connections on the unit The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant to water heat exchanger All source water connections on commercial units are fittings that...

Page 13: ...ove this level deposition will occur Less than 1 ppm above this level deposition will occur Less than 1 ppm above this level deposition will occur Erosion Suspended Solids Less than 10 ppm and filtered for max of 600 micron size Less than 10 ppm and filtered for max of 600 micron size Less than 10 ppm and filtered for max of 600 micron size Threshold Velocity Fresh Water 6 ft sec 6 ft sec 6 ft sec...

Page 14: ...ill the system with clean water Test the system water for acidity and treat as required to leave the water slightly alkaline pH 7 5 to 8 5 The specified percentage of antifreeze may also be added at this time Use commercial grade antifreeze designed for HVAC systems only Environol brand antifreeze is recommended Once the system has been filled with clean water and antifreeze if used precautions sh...

Page 15: ... 3 Close the cold water inlet valve to the water heater tank 4 Drain the tank by opening the valve on the bottom of the tank then open the pressure relief valve or hot water faucet 5 Flush the tank by opening the cold water inlet valve to the water heater to free the tank of sediments Close when draining water is clear 6 Disconnect the garden hose and remove the drain valve from the water heater 7...

Page 16: ...trical supply to the water heater adjust the temperature setting on the tank On tanks with both upper and lower elements the lower element should be turned down to the lowest setting approximately 100 F The upper element should be adjusted to 120 F to 130 F Depending upon the specific needs of the customer you may want to adjust the upper element differently On tanks with a single element lower th...

Page 17: ... National Electric Code whichever is applicable Power Connection Connect the incoming line voltage wires to L1 and L2 of the contactor for single phase unit Consult the Electrical Data tables for correct fuse sizes Electrical Connections For Aurora Base Control set SW2 1 FP1 on the printed circuit board for applications using a closed loop antifreeze solution to 15 F 9 4 C On applications using an...

Page 18: ...92 17 5 11 2 60 0 n a 2 0 13 2 16 0 25 208 230 60 3 187 253 13 9 8 9 58 0 34 8 2 8 11 7 13 9 20 460 60 3 414 506 6 5 4 2 28 0 16 8 1 4 5 6 6 7 10 15 036 208 230 60 1 187 253 22 0 14 1 73 0 26 0 3 5 17 6 21 1 35 265 60 1 238 292 17 5 11 2 60 0 n a 3 5 14 7 17 5 25 208 230 60 3 187 253 13 9 8 9 58 0 34 8 1 8 10 7 12 9 20 460 60 3 414 506 6 5 4 2 28 0 16 8 1 4 5 6 6 7 10 15 042 208 230 60 1 187 253 2...

Page 19: ... 7 6 27 5 32 5 50 208 230 60 3 187 253 21 2 13 6 83 1 49 9 7 6 21 2 24 6 35 460 60 3 414 506 9 5 6 1 41 0 24 6 4 0 10 1 11 6 15 060 208 230 60 1 187 253 41 2 26 4 134 0 53 0 7 6 34 0 40 6 60 208 230 60 3 187 253 24 9 16 0 110 0 66 0 7 6 23 6 27 6 40 460 60 3 414 506 12 1 7 8 52 0 31 2 4 0 11 8 13 8 20 070 208 230 60 1 187 253 44 2 28 3 178 0 51 0 7 6 35 9 43 0 70 208 230 60 3 187 253 30 0 19 2 136...

Page 20: ...87 253 21 2 13 6 83 1 49 9 4 0 17 6 21 0 30 460 60 3 414 506 9 5 6 1 41 0 24 6 4 1 10 2 11 7 15 048 208 230 60 1 187 253 31 0 19 9 109 0 38 0 7 0 26 9 31 9 50 208 230 60 3 187 253 21 2 13 6 83 1 49 9 7 0 20 6 24 0 35 460 60 3 414 506 9 5 6 1 41 0 24 6 6 9 13 0 14 5 20 060 208 230 60 1 187 253 41 2 26 4 134 0 47 0 7 0 33 4 40 0 60 208 230 60 3 187 253 24 9 16 0 110 0 66 0 7 0 23 0 27 0 40 460 60 3 ...

Page 21: ...5 1510 1330 M 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260 L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1175 070 H 11 x 10 1 2430 2400 2365 2330 2290 2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330 M 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260 L 2075 2050 2020 1995 1965 1940 1915 1885 1850...

Page 22: ...0 640 560 530 Low 1 695 645 595 575 550 520 495 455 420 400 030 High 5 9 x 7 1 2 1407 1381 1354 1327 1300 1267 1233 1201 1168 1131 1094 1009 Med High 4 W 1146 1134 1122 1111 1099 1085 1071 1062 1052 1042 1031 966 Med 3 Y1 1023 1012 1001 985 969 959 949 937 925 913 901 Med Low 2 978 962 946 934 922 907 891 882 872 858 843 Low 1 G 795 777 759 748 737 718 698 686 673 650 626 036 High 5 W 11 x 10 1 2 ...

Page 23: ... 10 1 1934 1910 1886 1871 1855 1827 1799 1780 1760 1747 1734 1700 1659 1617 Med High 4 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 Med 3 Y2 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 Med Low 2 Y1 1575 1560 1540 1520 1502 1487 1471 1448 1424 1409 1393 1351 1308 1266 Low 1 G 1454 1406 1358 1333 1308 1285 1261 1239 1217 1198 1179 1072 1002 988 064 ...

Page 24: ...2400 L M H 060 0 75 11 x 10 1 800 950 1100 1300 1500 1750 1950 2100 2300 L M H 070 0 75 11 x 10 1 800 950 1100 1300 1500 1750 1950 2100 2300 L M H 3 16 12 Dual Capacity Model Max ESP Blower Size Motor hp Air Flow DIP Switch Settings 1 2 3 4 5 6 7 8 9 10 11 12 026 0 50 9 x 7 1 2 400 500 600 700 800 900 1000 1100 1200 L M H 038 0 50 11 x 10 1 2 650 750 850 1000 1100 1200 1300 1400 1500 L M H 038 w 1...

Page 25: ...p This screen displays the current variable speed ECM settings It allows the technician to enter the setup screens to change the variable speed ECM settings Change the highlighted item using the and buttons and then press the button to select the item Setting Blower Speed Variable Speed ECM Blower Performance Data cont Variable Speed ECM Speed Setup These screens allow the technician to select the...

Page 26: ... On Time Compressor Short Cycle Delay Blower Off Delay Fault Recognition Delay High Pressure Start Up Bypass Low Pressure Fault Recognition Delay Low Pressure Start Up Bypass Low Water Air Coil Limit Fault Recognition Delay Low Water Air Coil Limit Fault Recognition Delay Condensate Overflow Thermostat Call Recognition Time Auxiliary Heat Staging Delay Emergency Heat Staging Delay Less than 1 seco...

Page 27: ... the CPU board if this option is not installed 5 Wire is provided with the unit but only connected to the X13 motor on dual capacity units Notes Accessory Relay Cycle with Blower Cycle with Compressor Water Valve Slow Open Outdoor Air Damper SW2 4 SW2 5 On On Off Off On Off Off On Operation Event Normal Mode Test Mode Random Start Delay Compressor On Delay Compressor Minimum On Time Compressor Sho...

Page 28: ...y to the PB1 1 if this option is not installed 12 Optional factory installed internal isolation valve 14 Network configurable input 15 Refer to the 5 Spd ECM Low Voltage Connection Table PGM Phase Guard Module RH Reheat Valve Coil 97P822 05 3 19 12 PB2 3 2 1 T CO T 2 1 3 Isolation Valve 6 1 12 5 13 2 9 10 4 14 7 15 3 11 24VAC R 24V COM C Alarm L Acc 1 X1 Acc 2 X2 Blower G Rev Valve O Comp Y1 Comp ...

Page 29: ... F1 Black F2 Black F3 Black F4 Black F5 Black F6 Black F7 Black F8 Black F9 Black F10 Black F11 Black F12 Black F13 Black F14 Black F15 Black F16 Black F17 Black F18 Black F19 Black F20 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Green Yellow 37 Red 33 Black 34 Brown 13 Violet 15 Yellow 18 Red 33 Black 34 Brown 13 Violet 15 Yellow 18 Yellow 35 Black White 36 Yellow 35 Black White 36 Yellow ...

Page 30: ...DI5 DI4 DI3 DI2 DI1 9VDC 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 D09 D08 D07 D0 6 D05 D04 D03 D02 D01 J8 J2 J10 J9 J7 A23 A13 A11 A21 A12 A25 A22 A32 A31 A35 A14 A24 A34 A33 A15 Yellow NOT USED 51 Yellow Wht 52 Connect to C on the Low Volt Terminal Board Connect to R on the Low Volt Terminal Board NOTE Reversing these two wires will cause the transformer breaker to trip Vo Gnd Vin Io Hu...

Page 31: ...second on and 1 second off Additionally when entering test mode LED1 red will flash the last lockout one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or by cycling the power NOTE Test mode will automatically be exited after 30 minutes ECM Configuration Mode The control is placed in the ECM configuratio...

Page 32: ...ult type identification display LED1 Red shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To reset lockout conditions with SW2 8 Off thermostat inputs Y1 Y2 W and DH must be removed for at least 3 seconds Lockout may also be reset by turning power off for at least 30 seconds or by enabling the emergency shutdo...

Page 33: ...he ECM will run on G speed until the G command is removed Regardless of blower input G from the thermostat the blower will remain on for 30 seconds at the end of each heating cycle Cooling Operation In all cooling operations the reversing valve directly tracks the O input Thus anytime the O input is present the reversing valve will be energized Cooling 1st Stage Y1 O The blower is started on G spe...

Page 34: ...M airflow settings The AID Tool simply plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault codes for the control These can also be read in plain English via the Aurora AID Tool Status LED LED3 Green Description of Operation Fault LED Green Normal Mode ON Control is Non func...

Page 35: ...y configured to read CO2 levels contact the factory for application assistance The FX10 control has unused analog and digital inputs for field installed items such as air temperature water temperature CO2 or current status switches The control has unused binary and PWM outputs that can be commanded over the BAS for field use An optional Medium User Interface MUI for control setup and advanced diag...

Page 36: ...ssor will not restart until the compressor short cycle time delay has been satisfied Low Pressure BI 3 The low pressure switch shall be a normally closed NC switch that monitors the systems refrigerant pressure The input shall be checked 15 seconds before compressor start up to be sure the pressure switch is closed and then ignored for the first 2 minutes after the compressor output BO 2 is enable...

Page 37: ...When the control receives a Y1 command BI 7 from the thermostat the low capacity compressor output BO2 will be enabled and the variable speed ECM blower will operate in medium speed When the control receives a Y2 command BI 8 from the thermostat the variable speed ECM blower will operate in high speed During the heating cycle the reversing valve will be commanded into the off position Cooling Cycl...

Page 38: ...proving sensors must be field supplied and installed BI 6 must be connected to PB2 position 3 see unit schematic in the field if no blower proving sensor is desired There is a configurable parameter available through a BAS network that must be enabled if this output is to be commanded over the BAS network NOTE For auto switch over BO 5 must be set to Emergency using the MUI MUI Alarm History Repor...

Page 39: ...min Rev Vlv Default Heating BO5 Mode Network CompStrtDly 90 sec SpaceT Offset 1 ºF DehumEnaDis Dis Acc1 Action On Comp Acc2 Action On Fan SW1 OFF SW2 OFF SW3 ON SW4 OFF SW5 OFF SW6 OFF SW7 ON SW8 OFF SW9 OFF SW10 ON SW11 OFF SW12 OFF ECM ALARM SUMMARY High Pressure Alarms Press right arrow key one time from Maintenance Menu No more than three speeds should be ON at one time Alarm Events Condensate...

Page 40: ... rate is correct by measuring the pressure drop through the heat exchanger using the P T plugs and comparing to the pressure drop table 6 Check the temperature of both the supply and discharge water Refer to Operating Parameters tables 7 Check for an air temperature drop of 15 F to 25 F across the air coil depending on the blower speed and entering water temperature 8 Decrease the cooling set poin...

Page 41: ...Hot Water Generation Suction Pressure psig Discharge Pres sure psig Superheat Subcooling Water Temp Rise F Air Temp Drop F DB 30 1 5 115 125 150 170 20 35 10 17 17 22 17 23 3 0 105 120 130 145 20 35 10 17 8 10 17 23 50 1 5 130 140 215 235 12 20 8 14 16 22 17 23 3 0 128 138 190 210 12 20 8 14 8 12 17 23 70 1 5 138 148 280 310 10 16 10 16 15 21 17 23 3 0 136 146 250 280 10 16 8 14 7 13 17 23 90 1 5 ...

Page 42: ...erformance based on entering air temperatures of 80º F DB 67º F WB Heating performance based on entering air temperature of 70º F DB 2 15 12 Second Stage Operation Entering Water Temp F Water Flow gpm ton Cooling No Hot Water Generation Suction Pressure psig Discharge Pres sure psig Superheat Subcooling Water Temp Rise F Air Temp Drop F DB 30 1 5 115 125 150 170 20 35 10 17 17 22 17 23 3 0 105 120...

Page 43: ...8 1 7 8 0 16 6 0 23 11 0 4 2 4 1 3 8 3 5 3 3 11 0 17 2 0 41 14 0 7 6 6 7 6 3 5 8 5 4 14 0 17 9 0 61 048 6 0 1 1 1 0 1 0 0 9 0 8 1 in 6 0 16 1 0 14 9 0 2 3 2 1 2 0 1 9 1 7 9 0 16 8 0 29 12 0 3 9 3 7 3 4 3 2 3 0 12 0 17 4 0 47 16 0 6 7 6 3 5 9 5 5 5 1 16 0 18 3 0 76 060 9 0 2 4 2 2 2 1 2 0 1 8 1 in 9 0 16 8 0 29 12 0 3 9 3 6 3 4 3 2 2 9 12 0 17 4 0 47 15 0 5 7 5 3 5 0 4 7 4 3 15 0 18 1 0 69 20 0 9 5...

Page 44: ... Insufficient Compressor Possible Bad Valves Low High Low High Normal High Low Low TXV Bulb Loss of Charge Low Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal Low High Low Low Scaled Coaxial Heat Exchanger Cooling High High High Normal Low Low Low Low Restricted Filter Drier Check temperature difference delta T across filter drier 7 6 10 Refrigerant Circuit Guide...

Page 45: ...73 0 85 n a 0 63 0 73 2 98 3 42 4 96 5 70 070 0 33 0 39 0 90 1 04 n a 0 56 0 64 2 34 2 70 3 48 4 00 Dual Capacity 026 1 21 1 39 1 52 1 75 1 38 1 58 2 02 2 32 2 00 2 30 8 00 9 20 n a 038 0 82 0 94 1 41 1 63 1 13 1 31 1 07 1 23 1 42 1 64 5 46 6 28 n a 049 0 48 0 56 1 73 1 99 n a 0 96 1 10 3 88 4 46 n a 064 0 36 0 42 1 52 1 74 n a 0 63 0 73 2 98 3 42 n a 072 0 32 0 36 1 72 1 98 n a 0 56 0 64 2 34 2 7...

Page 46: ... 5 72 0 070 12 0 52 4 66 9 78 1 91 1 89 5 83 0 15 0 37 9 53 7 69 8 82 9 83 4 91 2 89 4 82 7 76 8 18 0 38 1 54 3 70 9 84 8 83 8 91 9 90 3 83 6 77 6 3 16 12 Dual Capacity Model gpm Heat of Extraction HE MBtu h Heat of Rejection HR MBtu h 30 F 50 F 70 F 90 F 30 F 50 F 70 F 90 F 110 F 026 Part Load 3 0 14 0 18 8 22 8 26 7 26 6 24 3 5 0 10 2 14 8 19 8 24 0 24 7 26 8 26 7 24 2 22 2 7 0 10 3 15 1 20 1 24...

Page 47: ...he reversing valve coil If the unit operation is noisy 1 Check compressor for loosened mounting bolts Make sure compressor is floating free on its isolator mounts Check for tubing contact with the compressor or other surfaces Readjust it by bending slightly 2 Check screws on all panels 3 Check for chattering or humming in the contactor or relays due to low voltage or a defective holding coil Repla...

Page 48: ...______ VOLTS Total Amps Comp Fan n _____ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____ btu hr 7 EFFICIENCY Cooling EER p o q _____ EER Heating COP p o x 3 413 q _____ COP 8 SUPERHEAT S H SUBCOOLING S C COOLING HEATING Suction Pressure r ______ PSI r ______ PSI Suction Saturation Tempe...

Page 49: ...x 500 485 for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE COAX LOAD HEATING CYCLE ANALYSIS EXPANSION VALVE F AIR COIL F F F F PSI PSI BRINE IN BRINE OUT COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI SAT F F F LIQUID LINE Water to Water Applicatio...

Page 50: ...r be operated without a filter Condensate Drain In areas where airborne bacteria produce a slime in the drain pan it may be necessary to treat chemically to minimize the problem The condensate drain can pick up lint and dirt especially with dirty filters Inspect twice a year to avoid the possibility of overflow Blower Motors Blower motors are equipped with sealed ball bearings and require no perio...

Page 51: ...able 14S553 02 14S553 02 14S553 02 Not Available 5 Speed ECM Motor Blower 5 Spd ECM Motor 208 230 60 1 Not Available 14P536 01 14P537 01 5 Spd ECM Motor 265 60 1 Not Available 14P536 02 14P537 02 5 Spd ECM Motor 230 60 3 Not Available 14P536 01 14P537 01 5 Spd ECM Motor 460 60 3 Not Available 14P536 03 14P537 03 5 Spd ECM Blower Housing Not Available 53P512B01 53P515B01 PSC Motor Blower PSC Motor ...

Page 52: ...460 60 3 Not Available 14S553 02 14S553 02 14S553 02 Not Available 5 Speed ECM Motor Blower 5 Spd ECM Motor 208 230 60 1 Not Available 14P536 01 14P537 01 5 Spd ECM Motor 265 60 1 Not Available 14P536 02 14P537 02 5 Spd ECM Motor 230 60 3 Not Available 14P536 01 14P537 01 5 Spd ECM Motor 460 60 3 Not Available 14P536 03 14P537 03 5 Spd ECM Blower Housing Not Available 53P512B01 53P515B01 PSC Motor...

Page 53: ...ailable 14S553 01 14S553 01 Not Available Not Available 14S553 01 14S553 01 Not Available High Static VS ECM Motor 460 60 3 Not Available 14S553 02 14S553 02 Not Available Not Available 14S553 02 14S553 02 Not Available 5 Speed ECM Motor Blower 5 Spd ECM Motor 208 230 60 1 14P536 01 14P537 01 14P536 01 14P537 01 5 Spd ECM Motor 265 60 1 14P536 02 14P537 02 14P536 02 14P537 02 5 Spd ECM Motor 230 6...

Page 54: ...54 ENVISION2 COMPACT INSTALLATION MANUAL Notes ...

Page 55: ...New Variable Speed ECM Motor 08 Jan 2013 DS All Added IntelliStart Availability for 3 Phase Units 08 Jan 2013 DS 27 Replaced Wiring Diagram with Reheat Version 08 Jan 2013 DS 31 34 Updated Aurora Controls Description 08 Jan 2013 DS 51 53 Updated Service Parts Lists 08 Jan 2013 DS 55 Added Revision Guide 08 Jan 2013 DS ...

Page 56: ...ional Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifications without notice Product Envision2 Compact Type Water Source Geothermal Heat Pump Size Commercial 0 75 6 Ton Document Installation Manual IM1022AN 01 13 ...

Reviews: