Graphical Digital Panel Meter WPMZ-3 INSTRUCTION MANUAL
31
IM-0883-01
PatternSelect
You can store and set up 8 patterns (8 kinds) of various settings such as input and output with this unit, you can
select the pattern to save the setting in "PatternSelect".
The pattern number being set is displayed as "P5" on the upper right of the setting screen as shown below.
Operation:[MENU]
⇒
[Input]
⇒
[ProcessInputA][ProcessInputB]
⇒
[PatternSelect]
Setting value:Pattern1,Pattern 2,
・・・・・
Pattern 8
* At the time of opening the menu, the setting pattern is the value selected as operating on the measurement
screen.
* Since the setting pattern is common in each setting, "PatternSelect" such as output setting is also changed
when "PatternSelect" is changed by "ProcessInput A" or "ProcessInput B".
SensorPower
Select sensor power supply voltage.
If you change “SensorPower”, please close the menu once for reflecting the setting before connect a sensor.
Operation:[MENU]
⇒
[Input]
⇒
[ProcessInputA][ProcessInputB]
⇒
[SensorPower]
Setting value:12V (Default),24V
* In 1ch products, the maximum supply current is 100mA
@
12V, 50mA
@
24V
* In 2ch products, the maximum supply current (sum of Ach and Bch) is 100mA
@
12V, 50mA
@
24V
* When using both DC24V and DV12V in 2ch products, the maximum (sum of Ach and Bch) is 1.2Wmax
* When using both straingauge input and process input, in 2ch products, the maximum (sum of Ach and Bch) is
1.2Wmax
InputRange
Select input range of a sensor.
If you change “InputRange”, please close the menu once for reflecting the setting before connect a sensor.
*Be careful to connect input terminals. There are 2 terminals that one of it is for voltage input, and another is for
current input. (For wiring, please confirm "5. CONNECTING TERMINALS”.)
Operation:[MENU]
⇒
[Input]
⇒
[ProcessInputA][ProcessInputB]
⇒
[InputRange]
Setting value:0-5V,1-5V,±5V,0-10V(Default),±10V,0-20mA,4-20mA,±20mA
DecPoint
Select decimal point position of display value.
Operation:[MENU]
⇒
[Input]
⇒
[ProcessInputA][ProcessInputB]
⇒
[DecPoint]
Setting value:##### (Default),####.#,###.##,##.###,#.####