![WATANABE WPMZ-1 Instruction Manual Download Page 80](http://html1.mh-extra.com/html/watanabe/wpmz-1/wpmz-1_instruction-manual_3499830080.webp)
Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
79
IM-0882-03
SETTING VARIABLES
1st Layer
2nd Layer
3rd Layer
(setting items)
4th Layer (setting values)
Remarks
Initial values
Settable values
1. Input
DC InputA
DC InputB
Process
InputA
Process
InputB
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
InputRange
(DC)
Depend on model
Fixed by default value.
InputRange
(Process)
0
~
10V
0
~
5V/1
~
5V/±5V/0
~
10V
/±10V/0
~
20mA /4
~
20mA/±20mA
Select an input range.
*Offset and Fullscale setting are initialized
by changing this item.
SensorPower
12V
12V/24V
Switch sensor power supply
SamplingRate
50times/sec
(1 input product)
50times/sec
(2 input product)
4000 times/sec, 2000, 1000, 500, 200, 100,
20,10, 5, 2, 1,
Select sampling rate
(4000times/sec is enabled only 1 input
product)
MoveAve
None
None/2/4/8/16/32/64times
Set moving average of input.
Offset
DC:*Depend on
model
Process: 0
Go to screen of setting offset.
Fullscale
DC:*Depend on
model
Process: 10000
Go to screen of setting fullscale.
DecPoint
#####
#####/ #.####/ ##.###/ ###.##/ ####.#
*It is set to specific position
depends on each input ranges.
DispUnit
None
None/mV, mA, Pa, kg, N, etc./CustomUnit
*Unit that depends on input range is set.
InputCorrect
None
None/Linearize
LinearizePoint
1stIn
:
0
1stOut
:
0
2ndIn
:
1000
2ndOut
:
1000
……
16thIn
:
15000
16thOut
:
15000
Each: ±99999
Enable only if [InputCorrect] is [Linearize].
DispShift
0
±99999
Take over setting of [DecPoint].
TrackingZero
Interval
:
0
ActiveArea
:
0
Interval
:
0
~
99.99[sec]
ActiveArea
:
0
~
99999
Disable if setting value is 0[sec].
Take over setting of [DecPoint].
DispLimit
Lower
:
-99999
Upper
:
+99999
±99999
±99999
Take over setting of [DecPoint].
DispLoCut
0
0
~
99999
Cut both positive and negative.
InsDispStep
None
None/5steps/10steps
ZeroArea
0
0
~
99999[digit]
Disable if the value is 0[digit].
StableArea
0
0
~
99999[digit]
Disable if the value is 0[digit].
StableTime
0
0
~
99.99[sec]
Disable if the value is 0[sec].
2InputCalc
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
Expression
None
None/Add((A+B)+C)*K /Sub((B-A)+C)*K
/Mul((A*B)+C)*K /Div((B/A)+C)*K
/Ave (((A+B)/2)+C)*K
/HiSelect((Larger of A and B)+C)*K
/LoSelect((Smaller of A and B)+C)*K
/DifAbs(Abs of (B-A))+C)*K
/ErrRaito((A/B)-1)*K /Dens(B/(A+B))*K
/Add(A+B)*K+C /Sub(B-A)*K+C
/Mul(A*B)*K+C /Div(B/A)*K+C
Select an expression.
Const-C
C
:
0
C
:
±9.9999 x 10^(±5)
Coef-K
K
:
1
K
:
±9.9999
DecPoint
#####
#####/ #.####/ ##.###/ ###.##/ ####.#
DispUnit
None
None/mV, mA, Pa, kg, N, etc./CustomUnit
InsDispStep
None
None/5steps/10steps
DispLimit
Lower
:
-99999
Upper
:
+99999
±99999
±99999
Take over setting of [DecPoint].
ExternalCtrl
ExtCtrl 1
~
5 Func
None
None/CompareReset/HoldResetA,B,A&B
/DispHoldA,B,A&B/PeakHoldA,B,A&B
/BottomHoldA,B,A&B/AmpHoldA,B,A&B
/DevHoldA,B,A&B/AveHoldA,B,A&B
/DigitalZeroA,B,A&B/PatternChange1,2,3
/MonitorChange/TrendLog
Select a function which is attached to each
external control terminals.
Hold A/B
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
DispHoldMode
Normal
Normal/OneShot
HoldOffDelay
0.00
0.00
~
99.99[sec]
HoldMode
NormalHold
NormalHold/AreaHold
Select a mode of DispHold.
DevBaseValue
0
±99999
Take over setting of [DecPoint].
AveHoldCount
None
None/2/4/8/16/32/64times