Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
36
IM-0882-03
9.
INPUT ADVANCED SETTING
Here, the items of input setting which are not explained in the “BASIC SETTING” are explained.
DC InputA/B, ProcessInputA/B
SamplingRate
Select a sampling rate. Max rate of 1ch input products is 4000 sampling per sec(sps), and of 2ch input products is
2000 sps.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[SamplingRate]
Setting value:4000sps, 2000sps, 1000sps, 500sps, 200sps, 100sps, 50sps(Default), 20sps, 10sps, 5sps, 2sps, 1sps
MoveAve
Select the number of moving average.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[MoveAve]
Setting value:
None(Default), 2times, 4times, 8times, 16times, 32times, 64times
InputCorrect
Select linearize ON or OFF.
Linearize is a function to correct by maximum 16 points of polygonal line approximation when the sensor
characteristics are nonlinear.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[InputCorrect]
Setting value:
None(Default), Linearize
* Calculation processing of linearize is performed after calculation processing of “DispLoCut”.
(“DispLoCut” is to be described later)
LinearizePoint
*This setting item can be set only when “InputCorrect” is “Linearize”.
Set the correction value for 16 points of the linearize function.
After the second point, if both the pre-correction and post-correction set values are set to 0, it is judged to be a
termination, and the subsequent correction points are invalidated.
ex)
In the case of a sensor whose output is dull when the load is large.
(Display value is 0 to 8000 corresponding to 0 to 10 V input)
1stInput :
0
1stOutput:
0
2ndInput :
5000
2ndOutput:
5000
3rdInput :
5800
3rdOutput:
6000
4thInput :
6500
4thOutput:
7000
5thInput :
7000
5thOutput:
8000
6thInput :
0 (Disabled)
6thOutput:
0 (Disabled)
(7 to 16 points are disabled)
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[LinearizePoint]
Sensor load
Actual sensor output
Ideal sensor output
8.75V(Display value is 7000)
Output graph of sensor which output becomes nonlinear at high load
10V(Display value is 8000)
6.25V(Display value is 5000)
Linear up to display value 5000