Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
23
IM-0882-03
PatternSelect
You can store and set up 8 patterns (8 kinds) of various settings such as input and output with this unit, you can
select the pattern to save the setting in "PatternSelect".
The pattern number being set is displayed as "P5" on the upper right of the setting screen as shown below.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[PatternSelect]
Setting value:Pattern1,Pattern 2,
・・・・・
Pattern 8
* At the time of opening the menu, the setting pattern is the value selected as operating on the measurement
screen.
* Since the setting pattern is common in each setting, "PatternSelect" such as output setting is also changed
when "PatternSelect" is changed by "DC Input A/B" or "ProcessInput A/B".
SensorPower
Select sensor power supply voltage.
If you change “SensorPower”, please close the menu once for reflecting the setting before connect a sensor.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[SensorPower]
Setting value:12V (Default),24V
* In 1ch products, the maximum supply current is 100mA
@
12V, 50mA
@
24V
* In 2ch products, the maximum supply current (sum of Ach and Bch) is 100mA
@
12V, 50mA
@
24V
* When using both DC24V and DV12V in 2ch products, the maximum (sum of Ach and Bch) is 1.2Wmax