External cooling water system
It is recommended to divide the engines into several circuits in multi-engine installations. One
reason is of course redundancy, but it is also easier to tune the individual flows in a smaller
system. Malfunction due to entrained gases, or loss of cooling water in case of large leaks
can also be limited. In some installations it can be desirable to separate the HT circuit from
the LT circuit with a heat exchanger.
The external system shall be designed so that flows, pressures and temperatures are close
to the nominal values in Technical data and the cooling water is properly de-aerated.
Pipes with galvanized inner surfaces are not allowed in the fresh water cooling system. Some
cooling water additives react with zinc, forming harmful sludge. Zinc also becomes nobler
than iron at elevated temperatures, which causes severe corrosion of engine components.
9-6
DAAB605814
Wärtsilä 46F Product Guide
9. Cooling Water System
Summary of Contents for 46F Series
Page 1: ...Wärtsilä 46F PRODUCT GUIDE ...
Page 4: ...This page intentionally left blank ...
Page 8: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 86: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 154: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 170: ...This page intentionally left blank ...
Page 176: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 207: ...Fig 21 7 List of symbols DAAF406507 7 DAAB605814 21 5 21 ANNEX Wärtsilä 46F Product Guide ...