background image

1

warema_2012123_alhb_en_v5•2022-03-01

We reserve the right to make technical modifications

Safety instructions

ARNING

W

 

The electrical installation (assembly)/

dismantling must be performed by a cer-

tified electrician in accordance with the 

electrical installation regulations published 

by the Association of German Electrical 

Engineers (VDE 0100) or the standards 

and regulations of the country in which the 

device is being installed. The electrician 

must observe the installation instructions 

included with the electrical devices.

ARNING

W

 

If it can be assumed that safe operation is 

not possible, the device must not be com-

missioned or must be decommissioned if 

it is already in service. This assumption is 

justified if 

    

  The housing or the supply lines show 

signs of damage

    

  The device is no longer working. 

ARNING

W

 

For the safe functioning of the entire sys-

tem it is necessary that the drives, motor 

control units and power supplies are 

accurately coordinated with one another. 

Therefore, please contact our project man-

agement before planning.

ARNING

W

 

The control software loaded at the factory 

cannot be used for operation in a system. 

The control software loaded at the factory 

must be replaced by system-specific con-

trol software.

General information

Fig. 1 

BAline KNXMCM

The BAline product line is a system consisting of individual 

modules for room and building automation (such as sun 

shading systems, lighting, windows, HVAC, etc.). Each 

basic module (e.g. BAline KNXMCM) for bus coupling can 

be connected to up to 8 IO modules. The basic module 

can be combined with one or more IO modules as need-

ed. With this system, rooms can be automated in a wide 

variety of ways.

The BAline KNXMCM controller is a basic module for 

room and building automation to which various extension 

modules can be connected. The BAline KNXMCM device 

is equipped with a KNX TP1 interface. The device applica-

tion is loaded and monitored via a USB interface.

The extension modules can be connected using the 

BAline jumper, A maximum of 8 IO modules can be con-

nected to a BAline KNXMCM basic module.

Intended use

The BAline KNXMCM is a basic module for room and 

building automation. Any use other than the purpose 

described in these instructions requires manufacturer 

approval.

BAline KNXMCM

Installation instructions

Valid from 

1. March 2022

Keep for future use.

Summary of Contents for BAline KNXMCM

Page 1: ...l software loaded at the factory cannot be used for operation in a system The control software loaded at the factory must be replaced by system specific con trol software General information Fig 1 BAline KNXMCM The BAline product line is a system consisting of individual modules for room and building automation such as sun shading systems lighting windows HVAC etc Each basic module e g BAline KNXM...

Page 2: ...After the system specific control software is loaded the extension modules and the connected devices can be placed in service A software manual art no 2014978 is available for the BAline Studio PC software Contact your system integrator to request the manual Take suitable precautions in order to avoid damage through electrostatic discharges Maintenance There are no parts inside the device that req...

Page 3: ...temperature 25 70 C Rel humidity not condensing 10 40 85 Frel Degree of soiling 2 Connection 24 V DC supply Screw terminals RS485 bus supply of the following modules Jumper 24 V DC max 1 5 A KNX bus system Spring terminals Connection terminals 24 V DC supply max 2 5 mm2 KNX bus system 0 6 0 8 mm ø Miscellaneous Conformity Available at www warema com This device complies with the EMC directives for...

Page 4: ...m previous components YCYM 2x2x0 8 mm ø 9 8 7 6 24 V DC 2 5 A Power supply unit JY St Y 2x2x0 8 mm ø 0 V 24 V 0 V 24 V X1 X2 24V 24V 0V 0V Power BAline KNXMCM KNX KNX TP1 S1 D300 Status Power Attention The supply voltage of 24 V DC must be SELV voltage in accordance with VDE 0805 or EN 60950 Fig 5 Connecting the BAline KNXMCM ...

Reviews: