32
1.6 Potential problems and how to tackle them
Kind of operating prob-
lem
Possible reasons
Solution
Odour formation
Curing of the applied preven-
tive lacquer.
Steaming oil remains.
Operate the fire-place on a
low heating level according to
the instructions manual for a
few hours. Then heat up for
maximal performance for a
few hours.
Too little heating per-
formance
•
We chose too little per-
formance
•
Chimney draught is slight
•
Have the heating re-
quirement of the room
examined by an expert
•
Chimney draught shall
be at least 12 Pa, max.
for a short time
18 Pa
•
Check the tightness of
your chimney and also
that the doors of other
fire-places leading to the
same chimney are
closed and sealed prop-
erly. Make sure that the
chimney-cleaning joints
are sealed properly.
•
Too long and leaky
smoke tube
•
All the smoke tube joints
must be well sealed and
fireproof-isolated
•
Leakage at the door
glass
•
Check the sealing, close
the door properly. May
have to have the tighten-
ing flap renewed.
•
Usage of wet wood.
•
Use well dried wood
only.
Actions to be in chimney fire
Chimney fire may occur upon the improper cleaning of the chimney, the use of
inappropriate fuels (e.g. excessively wet wood) or the inadequate setting of the
burning air. In such cases, close the burning air at the fire, and call the fire service.
Never try to extinguish the fire with water!
Summary of Contents for Kamino Trendy RH6F
Page 13: ...13...
Page 16: ...16 Bild 1 RH6F 6kW Bild 2 RH8F 8kW Bild 3 RH8F Automatic 8kW RH6F 6kW RH8F 8kW RH8F Automatic...
Page 17: ...17 Bild 9 Bild 10 Bild 11...
Page 19: ...19...
Page 20: ...20...
Page 21: ...21...
Page 22: ...22...
Page 23: ...23...
Page 24: ...24...
Page 39: ...39 pic 9 pic 10 pic 11...
Page 55: ...55 Fig 9 Fig 10 Fig 11 Fig 12 Fig 13 Fig 14...
Page 74: ...74 Fig 1 RH6F 6KW Fig 2 RH8F 8KW Fig 3 RH8F Automatic NS RH6F 6kW RH8F 8kW RH8F Automatic NS...
Page 75: ...75 Fig 12 Fig 13 Fig 14 Fig 9 Fig 10 Fig 11...