Watlow Series 935B User’s Manual
Calibrating the 935B
Quick Calibration
Restore:
Press all three keys
simultaneously until
[tc50]
appears in the
display, press
.
once and
[`rSt]
will
appear in the display.
Press and hold
ß
,
the display will show
[``no]
, press
.
to
change display to
[`YES]
. Press and
hold
.
and
,
for 3 seconds to exit
the
[`CAL]
menu.
NOTE: Restore
Factory Calibration
[`rSt]
=
[`YES]
restores factory
calibration
values to all
calibration prompts.
Calibration Menu
[tc50]
✓
tc50
[tc00]
✓
tc00
[``tc]
✓
tc
[r`15]
✓
r15
[r380]
✓
r380
[`rSt]
✓
rst
Calibration Key Information
Calibration requires a precision millivolt source with
thermocouple compensation, an adjustable 0-10 volt source,
and a decade resistance box.
•
[tr50]
and
[tr00]
calibrate the thermocouple span.
•
[``tc]
calibrates the ambient compensation.
•
[r380]
and
[r`15]
calibrate the RTD span.
• When calibrating, calibrate all points for consistency in results.
• Allow the unit to warm up for 15 minutes before calibrating.
mV source = 50.000mV
mV source = 0.000mV
mV source = Temp. Compensation
Decade Box = 15.00 ohms
mV source = 380.00 ohms
• Store TC counts at 50.000mV
• Store ambient counts
at 32
°
F. Type J.
• Store low end RTD counts
• Store high end RTD counts
• Restore factory calibration
mV
source
–
1
+
2
C
O
M
–
3
R
T
S
+
4
1
+
5
2
+
6
7
8
IN
OUT
POWER
–
1
+
2
C
O
M
–
3
R
T
S
+
4
1
+
5
2
+
6
7
8
IN
OUT
POWER
Decade
Box
• Store TC counts at 0.000mV
Figure 8a -
Thermocouple Calibration
Figure 8b -
RTD Calibration