Section 5:
Electrical Installation
Alarm connection details
Models PD0046 - PD0360
•
To enable the alarm facility, it is recommended that a
suitable cable is brought into the controller via the rear
panel with a grommet. An external power source is
required.
•
Per Figures 5.5 (LED Controller) or 5.6 (DMC Controller),
connect the switching pole of an externally powered
alarm indication device to the corresponding terminals
of the controller’s alarm output.
For details regarding wiring of female DIN
connector refer to “How to wire a DIN connector”
on page 25.
Alarm Connection Details
Hirschmann GDS 207 industrial std DIN connector
or equivalent
Alarm Contact Rating (LED Controller)
3.0 AMPS 28VDC
Alarm Contact Rating (DMC Controller)
0.5 AMPS 24VDC
26
PRODRY PD0046 - PD0360 Instruction Manual
|
Walker Filtration
|
Section 5: Electrical Installation
Fig 5. 5 Alarm contact connections
(LED Controller)
LED Controller
Pin 3
Pin
Fig 5.6 Alarm contact connections
(DMC Controller)
Pin 1
Pin 2
DMC
Controller
1
2
3
1
2
3
DC Power
Supply
(Field Installed)
Remote
Visual or
Audible
Indicator
(Field Installed)
-VDC
+VDC
+24VDC
-24VDC/COM
Remote
Visual or
Audible
Indicator
(Field Installed)
Alarm connection details
Alarm Connection Details
Hirschmann GDS 207 industrial std DIN connector or equivalent
Alarm Contact Rating (LED Controller)
Alarm Contact Rating (DMC Controller)
3.0 AMPS 28VDC
0.5 AMPS 24VDC
To enable the alarm facility, it is recommended that a suitable
cable is brought into the controller via the rear panel with a
grommet. An external power source is required.
Per Figures 5.5 (LED Controller) or 5.6 (DMC Controller),
connect the switching pole of an externally powered alarm
indication device to the corresponding terminals of the
controller’s alarm output.
For details regarding wiring of female DIN connector
refer to “How to wire a DIN connector” on page 25.
•
•
Fig 5. 5 Alarm contact connections (LED Controller)
26
PRODRY PD0046 - PD0360 Instruction Manual
|
Walker Filtration
|
Section 5: Electrical Installation
Fig 5. 5 Alarm contact connections
(LED Controller)
LED Controller
Pin 3
Pin
Fig 5.6 Alarm contact connections
(DMC Controller)
Pin 1
Pin 2
DMC
Controller
1
2
3
1
2
3
DC Power
Supply
(Field Installed)
Remote
Visual or
Audible
Indicator
(Field Installed)
-VDC
+VDC
+24VDC
-24VDC/COM
Remote
Visual or
Audible
Indicator
(Field Installed)
Alarm connection details
Alarm Connection Details
Hirschmann GDS 207 industrial std DIN connector or equivalent
Alarm Contact Rating (LED Controller)
Alarm Contact Rating (DMC Controller)
3.0 AMPS 28VDC
0.5 AMPS 24VDC
To enable the alarm facility, it is recommended that a suitable
cable is brought into the controller via the rear panel with a
grommet. An external power source is required.
Per Figures 5.5 (LED Controller) or 5.6 (DMC Controller),
connect the switching pole of an externally powered alarm
indication device to the corresponding terminals of the
controller’s alarm output.
For details regarding wiring of female DIN connector
refer to “How to wire a DIN connector” on page 25.
•
•
Fig 5.6 Alarm contact connections (DMC Controller)