11.2.5 MODBUS Registers
Pos: 94.26 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbeschrei bung/F eldbuskommuni kation/M ODBU S/MOD BU S-Register (750- 880, -881, -352) - T eil 1.1 (0x102B) @ 7\mod_1265628629284_21.docx @ 49988 @ @ 1
Pos: 94.27 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbeschrei bung/F eldbuskommuni kation/M ODBU S/MOD BU S-Register ( x41) - T eil 1.1 (0x1030 und 0x1031) @ 7\mod_1265628290879_21.docx @ 49982 @ @ 1
Pos: null /Serie 750 (WAGO-I/O-SYST EM)/Funktionsbeschr eibung/F eldbuskommuni kation/M ODBU S/M ODBU S-Register (750-89x) - T eil 1.1 (0x1037) ohne 0x1035, -36 @ 33\mod_1540971502135_21.docx @ 506733 @ @ 1
Pos: 94.29 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbeschrei bung/F eldbuskommuni kation/M ODBU S/MOD BU S-Register ( x41) - T eil 1.2 (0x1050) @ 7\mod_1265628337132_21.docx @ 49985 @ @ 1
Pos: 94.30 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbeschrei bung/F eldbuskommuni kation/M ODBU S/MOD BU S-Register ( x41) - T eil 3 @ 3\mod_1235460292328_21.docx @ 27613 @ @ 1
Table 110: MODBUS Registers
Register
address
Acces
s
Length
(Word)
Description
0x1000
R/W
1
Watchdog time read/write
0x1001
R/W
1 … 2
Watchdog coding mask 1…16
0x1002
R/W
1
Watchdog coding mask 17…32
0x1003
R/W
1
Watchdog trigger
0x1004
R
1
Minimum trigger time
0x1005
R/W
1
Watchdog stop (Write sequence 0xAAAA, 0x5555)
0x1006
R
1
Watchdog status
0x1007
R/W
1
Restart watchdog (Write sequence 0x1)
0x1008
R/W
1
Stop watchdog (Write sequence 0x55AA or 0xAA55)
0x1009
R/W
1
MODBUS and HTTP close at watchdog time-out
0x100A
R/W
1
Watchdog configuration
0x100B
W
1
Save watchdog parameter ( Write sequence 0x55AA or 0xAA55)
0x1020
R
1 … 2
LED error code
0x1021
R
1
LED error argument
0x1022
R
1 … 4
Number of analog output data in the process image (in bits)
0x1023
R
1 … 3
Number of analog input data in the process image (in bits)
0x1024
R
1 … 2
Number of digital output data in the process image (in bits)
0x1025
R
1
Number of digital input data in the process image (in bits)
0x1028
R/W
1
Boot configuration
0x1029
R/W
1 … 9
MODBUS/TCP statistics (Write sequence 0x55AA or 0xAA55)
0x102A
R
1
Number of TCP connections
0x102B
W
1
KBUS Reset
0x1030
R/W
1
Configuration MODBUS/TCP time-out
0x1031
R
1 … 3
Read out the MAC-ID of the coupler/controller
0x1037
R/W
1
Modbus Response Delay (ms)
0x1050
R
3
Diagnosis of the connected I/O modules
0x2000
R
1 … 9
Constant 0x0000
0x2001
R
1 … 8
Constant 0xFFFF
0x2002
R
1 … 7
Constant 0x1234
0x2003
R
1 … 6
Constant 0xAAAA
0x2004
R
1 … 5
Constant 0x5555
0x2005
R
1 … 4
Constant 0x7FFF
0x2006
R
1 … 3
Constant 0x8000
0x2007
R
1 … 2
Constant 0x3FFF
0x2008
R
1
Constant 0x4000
0x2010
R
1
Firmware version
0x2011
R
1
Series code
0x2012
R
1
Coupler/controller code
0x2013
R
1
Firmware version major revision
0x2014
R
1
Firmware version minor revision