300 Appendix
WAGO-I/O-SYSTEM
750
758-874/000-131
WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Time referenced behavior
ACTUAL_ ADD
NEW_ ADD
IDENT_ NUMBER
ENABLE
CONFIRM
RESPONSE
Description
The function of slave addressing is activated when
ENABLE
switches to
TRUE
.
For reliable identification of the slave, the ID number must also be given. The
RESPONSE
output also indicates error-free or faulty execution when
CONFIRM
switches to
TRUE
.
The following states can be output on the
RESPONSE
output:
FUNCTION_OK
Function was executed without error
SERVICE_NOT_ACTIVATED
The 'Address Change' service is not
activated on the slave
NO_STATION_RESPONSE
No response received from the slave
NO_MASTER_TOKEN
Master does not currently have the token.
Bus short-circuit.
The diagnostics block is also used to control active communication of the newly
address slave with the master.
The
MODIFICATION
input can be used to select whether other address changes
of the slave are permitted or not.
MODIFICATION = FALSE:
Other address changes are permitted.
MODIFICATION = TRUE:
Other address changes are not permitted.