274 Appendix
WAGO-I/O-SYSTEM
750
758-874/000-131
WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Table 142: Description of the configuration scripts for " General SNMP information parameters "
Parameter
Status Call
Output/Input
Validity
Add new v3-
User
write
config_snmp
v3-edit=add
v3-auth-name=<value1>
v3-auth-type=<value2>
v3-auth-key=<value3>
v3-privacy=<value4>
v3-privacy-key=<value5>
v3-notification-
receiver=<value6>
Creating a new v3 user.
v3-auth-name: user name,
string without blank
characters, maximum 32
characters. The user name
may not have been
previously assigned.
Parameters:
User name (<value1> =
string)
Encryption type: (<value2>
=
none
,
MD5
, or
SHA
).
Key string for
authentication, (<value3> =
string with min. 8 and max.
32 characters).
Privacy encryption type
(<value4> =
none
,
DES
, or
AES
).
Privacy key string
(<value5> = string, min. 8
and max. 32 characters),
can be empty, in which case
the authentication key is
used. The
IP address of a trap receiver
is transmitted as the
notification receiver
(<value6> =
number.number.number.
number
). If no v3 traps are
to be sent, this entry is
omitted.
Delete v3-User
write
config_snmp
v3-edit=delete
v3-auth-name=<value>
Deleting a v3 user that has
been set up.
Because the doubled
allocation of the same user
name is prevented when
creating a user, the name is
sufficient to uniquely
identify a data set (<value>
= string).
after restart