26 Assembly
WAGO-PERSPECTO
762
762-2035, -2057, -2104, -2121, -2150 PERSPECTO VP, Visu-Panel
4.1.5
X5 - CAN 0 Interface
This interface is designed as an RJ45 connector. The interface is used to
communicate with CANopen-enabled modules.
The CAN 0 interface is designed with electrical isolation in accordance with
ISO 11898. A terminating resistor that can be switched on by relay is integrated in
the device in accordance with ISO11898.
More information is available from our description of the E5014 fieldbus systems.
The connected data cable must be shielded.
Figure 8: X5 – CAN 0 interface RJ-45
Table 10: X5 pin assignment
Pin
Assignment
Function
1
B_LA
CAN data low dominant
2
B_HA
CAN data high dominant
3
GND5V
Signal Ground extern 1
4 open
-
5
Do not use!
-
6
Do not use!
-
7 open
-
8 open
-