2AO FLD IOL CONV 0-10V
Table 45: Variables – Parameter Setting Errors
Name
Description
Subindex Data
Type
Length
Factory
Setting
Value Range
Parameter set-
ting error
Indicates the
parameter that
was set incor-
rectly at the
time of down-
load
0
ArrayT
10*32 bits 0
0 (OK)
786432 (device access
blocks, index 12)
11.2.5 Error Types
Table 46: Process Image – Error Types
Error Code
Name
Description
32785 d / 0x8011
Index does not exist
Access to an index that does not exist
32786 d / 0x8012
Subindex does not exist
Access to a subindex that does not exist
32800 d / 0x8020
Service is currently unavailable
The parameter cannot be accessed. The product
does not allow this in its current state.
32801 d / 0x8021
Service currently unavailable –
local operating mode
The parameter cannot be accessed, since the
product is currently in local operating mode.
32802 d / 0x8022
Service currently unavailable –
product operating mode
The parameter cannot be accessed, since the
product is currently in remote operating mode.
32803 d / 0x8023
Access denied
Write access to a read-only parameter
32816 d / 0x8030
Parameter value outside valid
range
The parameter value that was written is outside
the permissible value range.
32819 d / 0x8033
Parameter length overrun
The length of the parameter that was written is
greater than is allowed.
32820 d / 0x8034
Parameter length underrun
The length of the parameter that was written is
less than is allowed.
32821 d / 0x8035
Function unavailable
The product does not support the command that
was written
32822 d / 0x8036
Function currently unavailable
The product does not support the command that
was written in the current state.
32832 d / 0x8040
Invalid parameter set
The individual parameter value that was written
collides with the other parameter settings.
32833 d / 0x8041
Inconsistent parameter set
Inconsistencies were detected at the end of the
block parameter transfer. The product plausibility
check failed.
32898 d / 0x8082
Application not ready
Access was denied because the product is not
currently ready.
11.2.6 Events
Table 47: Process Image – Events
Code
Device status
Name
Type
Description
16384 d
0x4000
4 (error)
Temperature
error
Error
Overload
16912 d
0x4210
2 (Outside
specification)
Permissible
product tem-
perature ex-
ceeded
Warning
Locate and eliminate heat source
20480 d
0x5000
4 (error)
Hardware fault
in product
Error
Replace product
25376 d
0x6320
3 (Function
test)
Parameter er-
ror
Error
Check the datasheet and values.