136 • CANopen
Network
Communication
WAGO-I/O-SYSTEM
750
CANopen
4.3.4.4.19
Object 0x6444, Analog Output Error Value Integer
Idx
S-Idx
Name
Type
Attribute
Default Value
0x6444
0
Number analog output channels
(16Bit)
Unsigned8 RO
-
1
Error value 1. channel
Unsigned16
RW
0
.... ....
....
.... ....
128
Error value 128. channel
Unsigned16
RW
0
This object is used to define values that they are to assume in the event of an
error. Prerequisite being that the corresponding bit is set in object 0x6443.
4.3.4.4.20
Object 0x67FE, Error Behavior
Idx
S-Idx
Name
Type
Attribute
Default Value
0x67FE
0
Max. supported Sub-Index Unsigned8
RO
1
1 Communication
error
Unsigned8 RW
0
This object is used to define the status to which the module changes in the
event of a communication error (i.e.Node-Guarding failure).
Design Communication Error Entry:
Communication error
Action
0
Change to the
Pre-Operational
status (only when the cur-
rent status was
Operational
)
1
No status change
2
Change to the
Stopped
status
4.3.4.4.21 Object
0xA000-0xFFFF, Reserved Area
This reserved object directory area Index 0xA000-0xFFFF remains vacant for
the fieldbus coupler 750-337 and 750-338.