PROFINET IO 750-340
Diagnostics
WAGO-I/O-SYSTEM
750
PROFINET IO
3.1.7.2.3
Difference between Target and Actual Configuration
A diagnostics is performed by the coupler when there is a difference between
the module configuration of the I/O controller and the number of connected
sub-modules (I/O modules).
The
BlockType
in the head structure of the data set corresponds to the
value of the module differences (0x8104). The length gives information on the
differences between the configured and connected modules or sub-modules.
A structure head is used for the module differences.
Byte
offset
Data type
Description
0 / 1
0x00
0x00
2 / 3
DWORD
0x00 0x00
API
(
A
pplication
P
rocess
I
nstance) = 0
4 / 5
WORD
Number of slots with differences between target and actual
configuration
dependent on the number of data sets that follow
The number of data sets for each module that has been faulty configured is
stored in the head structure.
Byte
offset
Data type
Description
14 / 15
WORD
Module slot with set / actual deviation
Value range
1 ... 255
16 / 17
10 / 11
DWORD
Identification of the physically connected modules
12 / 13
WORD
Module status
0x0000 no module is connected
0x0001 Physically connected and configured module do not
correspond
0x0002 Physically connected and configured module correspond
but at least one sub-module is missing or does not
correspond.
0x0003 Physically connected and configured module do not
correspond but are compatible
0x0004
...
0xFFFF
reserved
14 / 15
WORD
Number of sub-module slots where a difference between the target and
actual configuration exists, otherwise 0
The data sets of faulty configured sub-modules are following the data set of
one module.