total of 6 words mapped into each image.
Word alignment is applied.
Table 441: 3-Phase Power Measurement Module
Input Process Image
Instance
Byte Destination
Description
High Byte
Low Byte
n
-
S0
Status byte 0
D1
D0
Input data word 1
n+1
-
S1
Status byte 1
D3
D2
Input data word 2
n+2
-
S2
Status byte 2
D5
D4
Input data word 3
The input modules represent 3x4 bytes and seize 3 Instances in Class (0x67).
Output Process Image
Instance
Byte Destination
Description
High Byte
Low Byte
n
-
C0
Control byte 0
D1
D0
Output data word 1
n+1
-
C1
Control byte 1
D3
D2
Output data word 2
n+2
-
C2
Control byte 2
D5
D4
Output data word 3
The input modules represent 3x4 bytes and seize 3 Instances in Class (0x68).
13.3.3.6 8 Channel Analog Input Modules
750-451
Table 442: 8 Channel Analog Input Modules for RTD’s
Input Process Image
Instance
Byte Destination
Description
High Byte
Low Byte
n
D1
D0
Measured Value Channel 1
n+1
D3
D2
Measured Value Channel 2
n+2
D5
D4
Measured Value Channel 3
n+3
D7
D6
Measured Value Channel 4
n+4
D9
D8
Measured Value Channel 5
n+5
D11
D10
Measured Value Channel 6
n+6
D13
D12
Measured Value Channel 7
n+7
D15
D14
Measured Value Channel 8