WAGO-I/O-SYSTEM 750
Commissioning 111
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
8.2.4
Assigning the IP Address with a PLC program
A PLC program can be used to assign a fixed IP address.
When assigning an address using a PLC program, this can be done using the
"Ethernet_Set_Network_Config" function block from the "Ethernet.lib" library
integrated in WAGO-I/O-
PRO
.
Additional Information about IP address assignment via a PLC program!
A detailed description of the library for the address assignment via a PLC
program, refer to the manual for the WAGO-I/O-
PRO
library "Ethernet.lib". This
can be found on the website under http://www.wago.com
Downloads
Additional documentation and Information on automation products
WAGO Software
WAGO-I/O-
PRO
/CODESYS
Additional Information
Libraries
Ethernet.lib!
8.2.5
Assigning the IP Address with a BootP Server
A BootP server can be used to assign a fixed IP address.
Assigning the IP address using a BootP server depends on the respective BootP
program. Handling is described in the respective manual for the program or in the
respective integrated help texts.
The BootP requests of port 1 and port 2 are dispatched sequentially and not
parallel. Two requests are sent for each port with an appropriate dead time,
afterwards it is changed on the other port.
Port 1 and port 2 may not be operated in the same network.
Set the address selection switch to 0 for active software configuration!
Set the address selection switch to 0 to disable the DIP switch.
If an access to the internal Web pages of WBM is already possible via an IP
address, then the software configuration via the WBM can be done.
In the default status, configuration via DHCP is activated.
If not yet been assigned IP address, you can otherwise use “WAGO Ethernet
Settings” or enable BootP in the
Network
tab of “WAGO Ethernet Settings”.
Restart the fieldbus node after adjusting the address selection switch to apply the
configuration changes.