108 Commissioning
WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
Set the address selection switch to 255 for active software configuration!
Set the address selection switch to 255 to disable the DIP switch and to enable
DHCP.
Restart the fieldbus node after adjusting the address selection switch to apply the
configuration changes.
Alternatively, DHCP will be enabled on the internal Web pages or via “WAGO
Ethernet Settings“.
DHCP must be enabled on the Web pages or in “WAGO Ethernet Settings”!
Note if an access to the internal Web pages of WBM is already possible via an IP
address, you enable DHCP on the "Port" HTML page of the WBM, so is assigned
via DHCP a new IP address. DHCP is not enabled by default when delivered.
In other case you can also enable DHCP via “WAGO Ethernet Settings” in the
Network
tab.
An IP address is automatically assigned after restarting the fieldbus node.
More information about reading the IP address
You can use “WAGO Ethernet Settings”, button
[Identify]
, via Service Interface
to read the IP addresses currently assigned.
8.2.2.2 Assigning the IP address permanently by option “use IP from
EEPROM“
IP stored in EEPROM must be used to assign the address permanently!
To apply the new IP address permanently in the fieldbus controller, the option
”use IP from EEPROM“ must be selected. Thus, the IP address is automatically
entered as static address and used in the EEPROM.
You can enable the option “use IP from EEPROM” in the Web-based
Management System.
1.
Open the
Web browser
on your client (such as the Microsoft Internet
Explorer) to have the HTML pages displayed.