Important Comments 

 

 

 Safety 

Notes 

 

 

  

WAGO-I/O-SYSTEM 

750 

  

I/O 

Modules 

1.4 Safety Notes 

 

Warning

 

Switch off the system prior to working on bus modules! 

In the event of deformed contacts, the module in question is to be replaced, as 
its functionality can no longer be ensured on a long-term basis. 

The components are not resistant against materials having seeping and 
insulating properties. Belonging to this group of materials is: e.g. aerosols, 
silicones, triglycerides (found in some hand creams). 

If it cannot be ruled out that these materials appear in the component 
environment, then additional measures are to be taken:  
- installation of the components into an appropriate enclosure 
- handling of the components only with clean tools and materials. 

 

Attention

 

Cleaning of soiled contacts may only be done with ethyl alcohol and leather 
cloths. Thereby, the ESD information is to be regarded. 

Do not use any contact spray. The spray may impair the functioning of the 
contact area. 

The WAGO-I/O-SYSTEM 750 and its components are an open system. It 
must only be assembled in housings, cabinets or in electrical operation 
rooms. Access must only be given via a key or tool to authorized qualified 
personnel. 

The relevant valid and applicable standards and guidelines concerning the 
installation of switch boxes are to be observed.  

 

ESD

 (Electrostatic Discharge) 

The modules are equipped with electronic components that may be destroyed 
by electrostatic discharge. When handling the modules, ensure that the 
environment (persons, workplace and packing) is well grounded. Avoid 
touching conductive components, e.g. gold contacts. 

 

1.5 Scope 

This manual describes the Digital Input Module 750-610 24 V DC Power 
Supply/Fuse/Diagn. of the m
odular WAGO-I/O-SYSTEM 750. 

Handling, assembly and start-up are described in the manual of the Fieldbus 
Coupler. Therefore this documentation is valid only in the connection with the 
appropriate manual.

Summary of Contents for I/O-SYSTEM 750-610

Page 1: ...Fieldbus Independent I O Modules 24 V DC Power Supply Fuse Diagn 750 610 Manual Version 1 0 2...

Page 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be...

Page 3: ...1 1 3 Intended Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 System Modules 7 2 1 1 750 610 24 V DC Power Supply Fuse Diagn 7 2 1 1 1 View 7 2 1 1 2 Desc...

Page 4: ...ufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual...

Page 5: ...ation ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient...

Page 6: ...rmation is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled...

Page 7: ...supply module 750 610 provides DC 24 V field side power to the downstream modules The power supply is derived from an external source via the 24 V 0 V and ground earth terminals The supply module 750...

Page 8: ...current of the supply module is 6 3 A When configuring the system it is important not to exceed the maximum sum current However if such a case should occur another supply module must be added The sup...

Page 9: ...750 610 24 V DC Power Supply Fuse Diagn 9 Schematic Diagram WAGO I O SYSTEM 750 I O Modules 2 1 1 4 Schematic Diagram 1 2 3 4 5 6 750 610 24V 0V 0V 24V Fig 2 1 1 3 Supply Module 750 610 g061001e...

Page 10: ...ller Manual EMC Immunity to interference CE acc to EN 50082 2 1996 EMC Emission of interference CE acc to EN 50081 1 1993 EMC Immunity to interference Ship building acc to Germanischer Lloyd 97 EMC Em...

Page 11: ...it Meaning B1 B0 fuse monitoring voltage monitoring off off No supply voltage is available at the CAGE CLAMP supply terminals off on Supply voltage is available and fuse is OK on off Supply voltage is...

Page 12: ...ept WAGO I O SYSTEM 750 I O Modules 626 602 610 624 612 601 610 609 611 602 601 24V 24V 24V 230V Potential 1 Potential 2 Potential 3 Field Electronic Field Field Field I O Modules Fieldbus Coupler Con...

Page 13: ...750 610 24 V DC Power Supply Fuse Diagn 13 Power supply concept WAGO I O SYSTEM 750 I O Modules...

Page 14: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Reviews: