750-597 8AO 0-10V/±10V DC
Manual
Version 1.2.0
7.1.1.6
Status Messages
This area provides information about occurring undervoltages of the field supply.
A requirement for displaying status message is that the checkbox for
the “Enable
diagnostic functions globally” function is activated in the
Module Settings
menu
item.
The status messages are determined for all channels from the status byte of
channel 1.
Click the button to expand the
Status Messages
window at the bottom of the
parameterization dialog to display the status messages.
Figure 29: Expanding the Status Messages Window
The following status messages with corresponding additional information are
displayed:
Table 30: Status Messages
– Possible Status Messages with Additional Information
Status message
Error type
Channel Status byte
Undervoltage field supply
Error
x
0x60
No error
Information
x
0x00
Click the
[Delete]
button to clear the status message history. The history is
automatically deleted if you interrupt the connection to the I/O module or close
the parameterization dialog.
7.1.1.7
Status Bar
The following information is displayed in the status bar:
•
Status indication with display of the currently executed action as text or the
respective error message if an error occurs
•
A progress bar is displayed as the actions are executed
•
Online status
•
IP address or COM interface
Figure 30: Status Bar in the Parameterization Dialog