26
Process Image
WAGO-I/O-SYSTEM 750
750-1425 8DI PTC
Manual
Version 1.1.0
Table 18: Output byte D0 – reserved
Output byte D0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
0
0
0
0
0
Reserved. The value is always 0 and may not be changed.
Table 19: Output byte D1 – channel shutoff
Output byte D1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
DI Off 8
DI Off 7
DI Off 6
DI Off 5 DI Off 4
DI Off 3
DI Off 2
DI Off 1
DI Off 1
PTC 1 – channel 1
0:
Channel ON
1:
Channel OFF
DI Off 2
PTC 2 – channel 2
0:
Channel ON
1:
Channel OFF
DI Off 3
PTC 3 – channel 3
0:
Channel ON
1:
Channel OFF
DI Off 4
PTC 4 – channel 4
0:
Channel ON
1:
Channel OFF
DI Off 5
PTC 5 – channel 5
0:
Channel ON
1:
Channel OFF
DI Off 6
PTC 6 – channel 6
0:
Channel ON
1:
Channel OFF
DI Off 7
PTC 7 – channel 7
0:
Channel ON
1:
Channel OFF
DI Off 8
PTC 8 – channel 8
0:
Channel ON
1:
Channel OFF
Pos: 64 /Serie 750 ( WAGO-I/O-SYST EM)/Prozessabbild Kl emmenbus/Hinweis: Prozessabbildmapping abhängig von FBK/PFC, mit Status-/C ontroll byte @ 4\mod_1242621308640_21.docx @ 33290 @ @ 1
Mapping of process data in the process image of fieldbus systems
The representation of the I/O modules’ process data in the process image depends
on the fieldbus coupler/controller used. Please take this information as well as the
particular design of the respective control/status bytes from the section “Fieldbus
Specific Design of the Process Data” included in the description concerning the
process image of the fieldbus coupler/controller used.