118 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-306 DeviceNet
TM
Fieldbus Coupler
Manual
Version 2.0.0
10.1.5.2.1.12 Module Configuration Object (0x80)
Instance 0
Table 100: Instance 0
Attributes
ID
Access Rights
Name
Data
Type
Value Description
1
get
Revision
UINT
1
Revision number of the class
definition for the “Identity
Object”
2
get
Max instance UINT
-
Maximum number of instances
of an object generated at the
time in this class level of the
device
Description of Instances
Table 101: Description of Instances
Instance ID Description
1
Reference to the first I/O module
…
65
Reference to the last possible I/O module
Instance 1 … 65
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data
Type
Description
1
Depending
on the type
of I/O
module
get
AOPOBJ_
VALUE
Array of
Byte
Description of the connected
I/O module (Instance 1 = Fieldbus
coupler/controller)
Bit 0: I/O module has inputs
Bit 1: I/O module has outputs
Bit 8…14: Internal data width (bit)
Bit 15: 0/1 Analog input/output
modules / digital input/output
modules
For analog input/output modules,
bits 0…14 designate the I/O
module type, e.g., 467 for I/O
module 750-467