22 Device Description
787-1668/0000-0080 Electronic Circuit Breaker
Manual
Version 1.1.0, valid from firmware 2.4.0
3.5.2
Technical Data for “Input"
Table 12: Technical Data for “Input"
Nominal input voltage
24 VDC
Input voltage range
18 … 30 VDC
Maximum residual ripple/
ripple for the input voltage
3 % with resistive load
Required input voltage at which the
channels are activated
(activation threshold)
20 V
Maximum continuous current for the
device
70 A
Maximum continuous current per
connector pole
40 A
Overvoltage protection
Suppressor diodes (33 V)
Closed current for open-circuit
operation at 24 V (default)
55 mA
Power loss for open-circuit operation at
24 V (default)
1.32 W
Input connectors
WAGO-
MULTI CONNECTION
SYSTEM
(
MCS
), 721 Series
Connection: 0.08 mm² … 2.5 mm²
(maximum 1.5 mm² with insulated
ferrule)
WAGO-
MULTI CONNECTION
SYSTEM
(
MCS)
, 831 Series
Connection: 0.5 mm² … 10 mm²
(maximum 6 mm² with insulated ferrule)