72
Process Image
WAGO-SPEEDWAY 767
767-5401 4DIO 24V DC 0.2A HS (4xM12)
Manual
Version 1.1.0
8.4.2
Output Data
The output data is transmitted from the fieldbus coupler to the I/O module. The
process image of the I/O module can contain process data with or without
diagnostic confirmation. If you have parameterized a synchronous diagnostic
confirmation, the process image has a size of 5 bytes. Otherwise, only 4-byte
process data is contained in the process image.
The process data and the diagnostic confirmation are structured as follows:
Table 41: DIO+counter, output data in the process image
Byte 0
7
0
Start value
\
-------------------
\/
-------------------
/
8 bit data. See section “Counter Function”.
Byte 1
7
0
Limit value
\
-------------------
\/
-------------------
/
8 bit data. See section “Counter Function”.
Byte 2 7
0
Counter control
\
-------------------
\/
-------------------
/
1
B
: See section “Counter Function”.
Byte 3 7
0
Digital outputs (Process data)
\
--------
\/
--------
/
1
B
: Output value = True
Byte 4 7
0
Diagnostic confirmation
| | | | | | | |
| | | | | | | 1
B
: Overtemperature on channel 1 conf.
| | | | | | 1
B
: Overtemperature on channel 2 confirmed
| | | | | 1
B
: Overtemperature on channel 3 confirmed
| | | | 1
B
: Overtemperature on channel 4 confirmed
|
|
|
|
|
|
1
B
: : Short circuit/overload field supply confirmed
on one or more channels confirmed
| | 1
B
: Not assigned, always 0
| 1
B
: Undervoltage U
LS
confirmed
1
B
: Undervoltage U
A
confirmed