WAGO-SPEEDWAY 767
Process Image
67
767-5401 4DIO 24V DC 0.2A HS (4xM12)
Manual
Version 1.1.0
8.2
Image in the DI Mode
8.2.1
Input Data
The input data is transmitted from the I/O module to the fieldbus coupler. The
process image of the I/O module can contain process data with or without
diagnostic messages. If you have parameterized a synchronous diagnostic, the
process image has a size of 2 bytes. Otherwise, only 1-byte process data is
contained in the process image.
The byte configuration is as follows:
Table 36: DI input data in the process image
Byte 0 7
0
Digital inputs (Process data)
\
--------
\/
--------
/
1
B
: Input value = True
Byte 1 7
0
Diagnostic message
| | | | | | | |
| | | | | | | 1
B
: Overtemperature on channel 1
| | | | | | 1
B
: Overtemperature on channel 2
| | | | | 1
B
: Overtemperature on channel 3
| | | | 1
B
: Overtemperature on channel 4
|
|
|
|
|
|
1
B
: Short circuit/overload field supply
on one or more channels
| | 1
B
: Not assigned, always 0
| 1
B
: Undervoltage U
LS
1
B
: Undervoltage U
A