54
Parameterizing
WAGO-SPEEDWAY 767
767-5401 4DIO 24V DC 0.2A HS (4xM12)
Manual
Version 1.1.0
Pos: 30.9 /Serie 767 (WAGO-SPEED WAY)/Par ametrieren/I/O-M odule/Parametri erung 767- 4801, - 02, -05, -06, 58xx, 7401 Globale Diagnosen @ 7\mod_1265877071562_21.docx @ 50302 @ @ 1
Table 28: Information about existing module diagnostics
Global Diagnostics
Diagnostics
Description
Low voltage of U
LS
Disabling the outputs.
If there is an undervoltage of U
A
and/or U
LS
, the
module outputs are disabled. Machine components can
be placed in a dangerous condition, as well as
personnel and machine put in danger.
If an undervoltage of the logic and sensor supply U
LS
of < 18 V occurs
on the module, the outputs are disabled and a corresponding diagnostic
is transmitted to the fieldbus coupler. The F-LED of the module
illuminates.
Low voltage of U
LS
Disabling the outputs.
If there is an undervoltage of U
A
and/or U
LS
, the
module outputs are disabled. Machine components can
be placed in a dangerous condition, as well as
personnel and machine put in danger.
If an undervoltage of the actuator supply U
A
of < 18 V occurs on the
module, the outputs are disabled and a corresponding diagnostic
transmitted to the fieldbus coupler. The module F-LED illuminates.
Pos: 30.10 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung Global e Di agnosen Kurzschl uss/Überlast und U nterbr echung Fel dversorgung @ 8\mod_1278394655719_21.docx @ 59061 @ @ 1
Short circuit/ overload
encoder supply
The module has detected a short circuit or overload of the encoder
supply (only possible when field supply is switched on).
Pos: 30.11 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung Kanaldi agnosen Ü bertemper atur 4808/5401 @ 13\mod_1343037033433_21.docx @ 100710 @ @ 1
Table 9: Information about an existing channel diagnostic
Channel Diagnostics
Diagnostics
Description
Overtemperature
The module has identified an overtemperature on the corresponding
channel (only enabled when the actuator output is switched on).
The reason may be: overtemperature or short circuit or overload of the
output circuit.
Pos: 30.12 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuter ung en/Sicherheitshinweise/Hinweis/Hi nweis: U nterbrechung S-BU S 48er @ 8\mod_1278393489593_21.docx @ 59044 @ @ 1
Interruption of the S-BUS
If there is an interruption of the S-BUS, the module is automatically put in STOP
mode. The module outputs are disabled.
Pos: 30.13 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1