Process Image
WAGO-SPEEDWAY 767
767-4801/000-800 8DO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
Pos: 38 /Serie 767 ( WAGO-SPEED WAY)/Prozessabbild/I/O-Module/Prozessabbil d 767-48xx Ei ngangsdaten @ 5\mod_1249368072484_21.docx @ 40151 @ 2 @ 1
8.2
Input Data
The image for the process data, which are sent from the I/O module to the fieldbus
coupler, has a size of 0 byte. If you configure synchronous diagnostic data for the
I/O module, the process image has a size of 4 bytes.
The diagnostic message is structured as follows:
Table 30: Input data in the process image
Byte 0
7
0
Diagnostic message
| | | | | | | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1
B
: Actuator short circuit/overload on
channel 1
|
|
|
|
|
|
|
|
|
|
|
|
1
B
: Actuator short circuit/overload on
channel 2
| | | | | 1
B
: Actuator short circuit/overload on channel 3
| | | | 1
B
: Actuator short circuit/overload on channel 4
| | | 1
B
: Actuator short circuit/overload on channel 5
| | 1
B
: Actuator short circuit/overload on channel 6
| 1
B
: Actuator short circuit/overload on channel 7
1
B
: Actuator short circuit/overload on channel 8
Byte 1 7
0
Diagnostic message
| | | | | | | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1
B
: Actuator supply open load on
channel 1
| | | | | | 1
B
: Actuator supply open load on channel 2
| | | | | 1
B
: Actuator supply open load on channel 3
| | | | 1
B
: Actuator supply open load on channel 4
| | | 1
B
: Actuator supply open load on channel 5
| | 1
B
: Actuator supply open load on channel 6
| 1
B
: Actuator supply open load on channel 7
1
B
: Actuator supply open load on channel 8
Byte 2 7
0
Diagnostic message
| | | | | | | |
| | | | | | | 1
B
: Overtemperature on channel 1
| | | | | | 1
B
: Overtemperature on channel 2
| | | | | 1
B
: Overtemperature on channel 3
| | | | 1
B
: Overtemperature on channel 4
| | | 1
B
: Overtemperature on channel 5
| | 1
B
: Overtemperature on channel 6
| 1
B
: Overtemperature on channel 7
1
B
: Overtemperature on channel 8