Table 52: Port-Specific Diagnostics
Node Name
Node Class
Access
Description
DiagnosticsPin1, Di-
agnosticsPin2, Diag-
nosticsPin4
Variable
Read
Diagnostics on pin 1, pin 2 or pin 4; the nu-
merical value contains bit-coded informa-
tion:
Bit 0: short circuit
Bit 1: overload protection
Bit 2: overtemperature protection
Bit 3: overvoltage protection
Bit 4: overcurrent
Bit 5: undercurrent
Bit 6: overtemperature
Bit 7: undertemperature
Bit 8: overvoltage
Bit 9: undervoltage
Bit 10: watchdog
0: diagnostics inactive
1: diagnostics active
10.3.3.1.7 Read Statistics
The OPC UA server provides nodes with statistical information. For example, the OPC
UA client can read out the maximum measured current on pin 1 of a port in the
MaxCur-
rentPin1
node.
The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector >
PortXX > Statistics > Current / Temperature / Voltage
The following table lists port-specific statistical information:
Table 53: Port Specific Statistical Information
Measurement
Node Name
Node Class
Access
Description
Current
MaxCurrentPin1
Variable
Read
Maximum current on
pin 1 since the value
was reset; unit: mA
MaxCurrentPin2
Variable
Read
Maximum current on
pin 2 since the value
was reset; unit: mA
MaxCurrentPin4
Variable
Read
Maximum current on
pin 4 since the value
was reset; unit: mA
MinCurrentPin1
Variable
Read
Minimum current on
pin 1
MinCurrentPin2
Variable
Read
Minimum current on
pin 2
MinCurrentPin4
Variable
Read
Minimum current on
pin 4
Temperature
MaxTemperature-
Pin1
Variable
Read
Maximum tempera-
ture on pin 1 since
the value was reset;
unit: °C