10.3.3.1.2 Setting Device Parameters
The OPC UA server provides nodes with configuration parameters for the device. For ex-
ample, the OPC UA client can read out the upper limiting value for temperature in the
OverTemperature
node.
The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector > Di-
agnostics > Configuration
The following table lists device-specific configuration parameters.
Table 46: Device-Specific Configuration Parameters
Node Name
Node Class
Access Default Description
CurrentHysteresis
Variable
Read
10 mA
Current hysteresis; unit: mA
If the current exceeds the limiting value, the cur-
rent must fall back below the limiting value by the
hysteresis value before the diagnosis is revoked.
OverTemperature
Variable
Read
70 °C
Upper limiting value for the temperature of a port;
unit: 0.1 °C
OverVoltage1L
Variable
Read
30000
mV
Upper limiting value for the voltage in supply ca-
ble 1; pins with the following functions can be
monitored: L+, DI, DO, DIO, IO-Link; unit: mV
OverVoltage2L
Variable
Read
30000
mV
Upper limiting value for the voltage in supply ca-
ble 2; unit: mV
TemperatureHysteresis
Variable
Read
2 °C
Temperature hysteresis; unit: 0.1 °C
If the temperature exceeds the limiting value, the
temperature must fall back below the limiting
value by the hysteresis value before the diagno-
sis is revoked.
UnderTemperature
Variable
Read
−25 °C Lower limiting value for the temperature of a port;
unit: 0.1 °C
UnderVoltage1L
Variable
Read
18000
mV
Lower limiting value for the voltage in supply ca-
ble 1; pins with the following functions can be
monitored: L+, DI, DO, DIO, IO-Link; unit: mV
UnderVoltage2L
Variable
Read
18000
mV
Lower limiting value for the voltage in supply ca-
ble 2; unit: mV
VoltageHysteresis
Variable
Read
300 mV Voltage hysteresis; unit: mA
If the voltage exceeds the limiting value, the volt-
age must fall back below the limiting value by the
hysteresis value before the diagnosis is revoked.
10.3.3.1.3 Setting Port Parameters
The OPC UA server provides nodes with configuration parameters for each port.
The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector > Di-
agnostics > PortXX > Configuration
The following table lists port-specific configuration parameters.