765-1205/0100-0000
Properties
Product manual | Version: 1.0.0
21
8DIO FLD EC DC 24V 2.0A
Table 16: EtherCAT
®
Slave
Parameters
Value
Input data
4 bytes
Output data
3 bytes
Type
Complex slave
Features
Emergency
SYNC manager
4
Supported protocols
SDO server
CoE (CANopen over EtherCAT)
EoE (Ethernet over EtherCAT)
FoE (File Access over EtherCAT)
Transmission rate
100 MBit/s
Data transport layer
ETHERNET II, IEEE 802.3
Interface type
100BASE-TX, potential-free
Autonegotiation, autocrossover
Yes
Table 17: OPC UA Server
Parameters
Value
OPC UA Server
Manufacturer-specific information models with diag-
nostic functions:
ü
http://www.wago.com/UA/DigitalConnector/
ü
http://www.wago.com/UA/Diagnostics/
Server profile
Micro Embedded Device
Protocol
OPC UA TCP
User access
Anonymous (read access only)
Username/password (read and write access)
Number of sessions
2
Number of subscriptions per session
2
Number of “monitored items” per session
20
Data coding
UA binary
Table 18: Communication – Bluetooth
®
transmitter
Property
Value
Modulation
GFSK
Data rate
1 Mbit/s
Operating frequency
2402 ... 2480 MHz
Maximum power, including tune-up tolerance
Output power: +8 dBm
Tolerance: +2 dBm / −3 dBm
Antenna type
PCB monopole
Maximum antenna gain
1.25 dBi
We declare that we meet the EN 62479 standard with respect to the limiting value for low
powers less than 20 mW. Therefore, the product fundamentally corresponds to the Euro-
pean limiting values for high-frequency radiation.
4.5 Derating
The following figure shows the maximum permissible current (I) that can flow into the
product as a function of the surrounding air temperature (T).