761-210 Telecontrol Module Compact
Manual
Version 2.0.0
Figure 19: Configuring digital inputs 5 … 8 (when provided)
Table 22: Configuring of digital inputs
Counters (only for digital inputs 1 … 4)
Counters
Check this box to use the selected digital input as a counter
input.
To activate the counter click the button
[Activate]
. This
button is only active when the input is used as a counter
input. On completion of configuration, the counter can be
activated/deactivated during operation via the visualization
system.
This function is available starting with Firmware Version FW
2.33.
Starting value
In this field enter the starting value for the counter.
This field is only active when the input is used as a counter
input.
End value
In this field enter the end value for the counter.
This field is only active when the input is used as a counter
input.
If the starting value is less than the end value the counter will
count upward. If the end value is exceeded, the counting
process is restarted from the starting value.
If the starting value is greater than the end value the counter
will count downward. If counting then continues below the
end value, the counting process is restarted from the starting
value.