750-643 [MP-Bus Master Module]
•
27
Network
structure
WAGO-I/O-SYSTEM 750
I/O Modules
2.1.1.9.4 Topology
There are no restrictions with regard to the network topology. Star, ring and
tree structures are possible as well as mixed forms.
Slave
Slave
Slave
Slave
Slave
Slave
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
MP-
Master
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
MP-
Master
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Sensor
Slave
Slave
Slave
Slave
Slave
Slave
Slave
MP-
Master
Sensor
Slave
Slave
Sensor
Slave
Sensor
Fig. 2.1.1-6: MP-Bus topologies
g064306x
One sensor can be connected per drive.
Drive
Connectable sensor
MFT
Active sensor (Output DC 0-32 V),
Switch ON/OFF
MFT2
Active sensor (Output DC 0-32 V),
Passive resistive sensor (e.g. PT1000),
Switch ON/OFF
2.1.1.9.5 External MP-Bus Master (hand held)
The module detects whether an external MP-Bus master has been connected
by means of the "Enable Handheld" input. The Belimo MFT parameterizing
unit MFT-H and the MFT-PC tool are external MP-Bus masters for the
module.
24 V
GND
MP-Bus
MP
MP
24 V 24 V
0 V
0 V
En
En
75
0-
6
43
Enable
GND
MP-Bus
max.
8
modules
alternative
Fig. 2.1.1-7: Connecting an external MP-Bus master (e.g. hand held)
g064308e