18
•
750-643 [MP-Bus Master Module]
Data
transfer
WAGO-I/O-SYSTEM
750
I/O
Modules
2.1.1.8.1 Message codes for the extended control byte
MSG_CODE
DPID
DATA
Description
Null
message
0 D0-4 not
used
0 D5 TNO
1 D0-4 not
used
F2K_NULL 0
1 D5 TNO
MP-Bus driver request for initialization
0 D0-4 not
used
0 D5 TNO
1 D0-4 not
used
F2K_INIT 1
1 D5 TNO
Module test (transparent communication). Number of data from
D1 are transmitted and received again, and reported back via
K2F_TEST.
0
D0
Number of data to be sent max. 9 (0D1-5 and 1D0-3)
0
D1-4
Transmission data (any byte stream)
0 D5 TNO
1
D0-3
Transmission data (any byte stream)
1 D4 not
used
F2K_TEST 2
1 D5 TNO
Transmission request. MP-Bus communication for broadcast
telegrams.
The module returns the message code K2F_COM_T0 as a reply.
0
D0-4
MP-Bus telegram according to specification without length and
cross parity.
0 D5 TNO
1
D0-4
MP-Bus telegram according to specification without length and
cross parity.
F2K_COM_T0 3
1 D5 TNO
Communications request for request-response telegrams.
0
D0-4
MP-Bus telegram according to specification without length and
cross parity.
0 D5 TNO
1
D0-4
MP-Bus telegram according to specification without length and
cross parity.
F2K_COM_T1 4
1 D5 TNO
Communications request for request-response telegrams.
The module returns the transmitted MP-Bus command byte with
the reply.
0
D0-4
MP-Bus telegram according to specification without length and
cross parity.
0 D5 TNO
1
D0-4
MP-Bus telegram according to specification without length and
cross parity.
F2K_COM_T2 5
1 D5 TNO
Call function macro.
0
D0
Function macro ID.
0
D1-4
Function macro parameters.
0 D5 TNO
1
D0-4
Function macro parameters.
F2K_FM 6
1 D5 TNO